To Get A Device Log - Carrier TruVu UCXP683T Installation And Startup Manual

Table of Contents

Advertisement

Troubleshooting
Anything other than No Fault Detected indicates an error. See the table below to determine the error and
5
possible actions to take.
Reliability
description
Communication
Failure
Configuration
Error
Over Range
No Output
No Sensor
Shorted Loop
Open Loop
Unreliable Other

To get a Device Log

If Carrier Control Systems Support instructs you to get the controller's Device Log containing diagnostic
information for troubleshooting:
Select the TV-UCXP683T in the i-Vu® navigation tree.
1
On the Properties page, click Device Log.
2
NOTE You can click Device Log Archive to download a file containing multiple Device Logs to your computer. This
also contains any network packet captures that have been run from the Network Diagnostics - Packet Captures
(page 40) driver page.
TruVu™ UCXP683T
Installation and Start-up Guide
Possible error
Expander is not connected to the
controller.
The expander has no power.
The controller is offline.
The microblock's I/O Type and
Sensor/Actuator Type are not
compatible.
The output's DIP switch setting does
not match the connected device.
Invalid expander address or I/O
number.
Input exceeds the Min/Max limits.
Output's Hand-Auto-Off switch is in
Hand or Off position.
No device is attached to the output.
Internal voltage feedback does not
correspond with commanded value.
Internal current feedback does not
correspond with commanded value.
Feedback from the expander does not
correspond with commanded value (for
example, the output relay is not in
commanded state).
Verify that...
The expander is connected to the
controller's I/O bus edge connector or
wired to the I/O Bus port.
The expander has power.
The I/O Type and Sensor/Actuator Type
combination is valid for the I/O number
and microblock type.
The DIP switch setting is appropriate for
the output and microblock type.
The expander is present and functional at
the address shown in the i-Vu® interface
and that I/O number is valid.
The input is within the Min/Max limits.
The expander's Hand-Auto-Off switch is in
the Auto position.
The device is present and functioning.
The load on the output is within the valid
range.
A voltage/current source has not been
connected to an output.
The load on the output is within the valid
range.
A voltage/current source has not been
connected to an output.
Expander may be faulty. Contact
Technical Support.