Appendix - Module Status field descriptions

Field
ADDRESS BINDING
Date/Time
Model Name
Device Instance
Driver built
Downloaded by
Application Software Version
Data Partition Version
# PRGs initialized
# PRGs running
Driver version
Reset Counters:
Power failures
Commanded boots
System errors
S/W Watchdog
timeouts
H/W Watchdog
timeouts
System status
Network status
System error message history
TruVu™ UCXP683T
Installation and Start-up Guide
Description
The controller's:
Device Instance
Network number
MAC address
See To set up the controller through the Service Port (page 46).
Date and time the Modstat was run
Identifies the Product Type
A unique ID assigned to the controller
When the driver was built
When and where the last download was performed
The application software version that is in the BACnet device.
Not applicable to this device.
If applicable, the number of control programs that were downloaded vs. the
number that are running. If these numbers are not the same, the controller
has a problem such as lack of memory.
The name, version, and date of the driver, as well as all the bundles and
versions.
The number of times each of the following events have occurred since the last
time the controller was commanded to clear the reset counters.
See NOTE below this table.
Interruption of incoming power
Includes commands issued from the i-Vu® interface such as the zap manual
command, plus commands issued during a memory download.
Error in the controller's firmware or hardware
Watchdog is firmware that monitors the application firmware for normal
operation. If the watchdog firmware detects a problem, it restarts the
application firmware.
H/W Watchdog will restart the controller if it detects a severe problem with the
controller's operating system
Gives the current status of the controller's operation. See LEDs (page 56) for
all possible conditions.
Gives the current status of the controller's networks. See LEDs (page 56) for
all possible conditions.
High-severity errors since the last memory download. Shows the most recent
10 messages.
See NOTE below this table.