Wiring devices to the TV-UCXP683T's Act Net port

Supports a combination of up to 5 Act Net addresses, as follows:
Address 1 is reserved for the Carrier actuator
Address 2 and 3 are reserved for the VAV Zone II Secondary Duct
Address 4 and 5 for i-Vu® Smart Valves
Maximum power available for Act Net devices:
AC supply - 25 VA (1 A)
DC supply - 15W (0.625A)
Use an external transformer if your devices exceed the maximum power.
CAUTIONS
If the power source for the Act Net devices require a connection to earth ground, you must place it in the
same control panel as the TV-UCXP683T controller, so that it shares a common earth ground reference,
thereby reducing the potential for ground loops.
A remote Act Net power source, installed near the Act Net devices, should be floating (no local
connection to earth ground).
The TV-UCXP683T provides an orange, three-pin removable screw terminal connector for the Act Net port.
Be careful to wire the Act Net port terminals on the controller to the matching terminal on the supported device.
They may not be in the same order. See example below.
TruVu™ UCXP683T
Installation and Start-up Guide
Wiring devices to the TV-UCXP683T's Act Net port
19