Shutter Actuators Ac 230 V And Roller Shutter Actuator: Electrical Connection - Gira KNX 1039 00 Operating Instructions Manual

Blind actuator 4-gang 230 v ac
Table of Contents

Advertisement

Blind actuator
Drives for venting louvers or windows must be connected in such a way that
they open in travel direction "UP " and close in travel direction "DOWN".
7.4
Shutter actuators AC 230 V and roller shutter actuator: electrical
connection
Connecting the device without automatic operation time detection
Connect mains voltage supply (see figure 4).
Connecting the motors (see figure 5).
Mark 230 V use on label (see figure 5).
The N conductor connections (14) serve only to detect the operation time and
do not provide any N potential.
If motors with high-impedance inputs are connected, then the corresponding N
conductor can be connected. The associated output must not be under current
for a longer period without interruption due to retriggering. This can lead to im-
permissible heating of the device. Observe maximum duty cycle (see chapter
"Technical data").