Information for electrically skilled persons

6.1

Mounting and electrical connection

DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
Mounting the device
Enter or scan the device certificate and add it to the project. A high resolution
camera should be used to scan the QR code.
The device certificate should be removed from the device during mounting.
Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
Mount device on DIN rail.
Connecting the device
Connect either AC 230 V or AC 24 V valve drives to all the outputs.
Only connect valve drives with the same characteristics to each output (deenergised
closed/opened).
Do not connect any other loads.
Connect valve drives for frost-sensitive rooms to outputs A1 and A4. These are
switched off last in the event of overload.
Do not exceed maximum number of valve drives per output.
Observe the technical data of the valve drives used.
Do not connect the neutral conductor from the output terminals through to additional
devices.
Connect AC 230 V valve drives according to the connection diagram
(see figure 3).