4

Information for electrically skilled persons

DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
4.1

Mounting and electrical connection

DANGER!
When connecting the bus/extensions and mains voltage wires in a shared appliance
box, the bus line may come into contact with the mains voltage.
This endangers the safety of the entire installation. People at remote devices may
also receive an electric shock.
Do not place bus/extensions and mains voltage terminals in a shared connection
compartment. Use an appliance box with a fixed partition wall or separate appliance
boxes.
Connecting and fitting the device
Enter or scan the device certificate and add it to the project. A high resolution
camera should be used to scan the QR code.
The device certificate should be removed from the device during mounting.
Document all passwords and keep them safe.
Mounting in suitable appliance box (recommendation: electronic device box with par-
tition). Observe cable routing and spacing (see figure 3)!