Context
Prerequisites
● Before replacing a battery pack, ensure that the ESS is powered off. Otherwise,
electric shocks may occur.
● Wear personal protective equipment and use dedicated insulated tools to avoid
electric shocks or short circuits.
● Do not smoke or have an open flame around batteries.
● Do not use wet cloth to clean exposed copper bars or other conductive parts.
● Do not use water or any solvent to clean batteries.
Issue 04 (2023-06-30)
4
NO TE
The Company is responsible for maintaining and transferring abnormal battery packs within
the warranty scope. For a battery pack whose warranty period has expired, contact the local
recycling agencies for handling.
Fault locating:
a.
Log in to the SmartLogger WebUI, CMU WebUI, FusionSolar app, or
management system to view alarm information.
b.
Locate the faulty battery pack based on the alarm information.
c.
Refer to the alarm handling suggestions in the alarm list.
Tools: insulated torque socket wrench (including an extension bar), battery
installation tray kit (installation kit for short), infrared thermometer
Power off the ESS. For details, see
At least four persons are required to replace the component.
D ANGER
Copyright © Huawei Digital Power Technologies Co., Ltd.

Replacing a Battery Pack

2.2 Powering Off a Single
4 Replacing a Battery Pack
ESS.