LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
Maintenance Manual
Figure 8-19 Searching for devices
Step 8 Click Monitoring, select the old device, choose Running Param. > Setting > All >
Batch configurations, select the new device, and click Confirm to synchronize
data to the new device.
Issue 04 (2023-06-30)
NO TE
● During the process of Search for Device, do not perform upgrade operations (such as
upgrading through the app, management system, or WebUI).
● When you click Search for Device, cable connections (DC and AC) will be checked
before device search (not applicable to third-party devices), and device addresses will be
automatically allocated.
● After the cable connection check and device search are complete, if a cable connection
alarm is generated, you can click the alarm icon
information.
● If an alarm is generated when the cable connection check fails, click the alarm icon
to view the alarm cause and handling suggestions. After the fault is rectified, check the
cable connections again.
● After the cable connection check and device search are complete, click
corresponding topology information.
● After a device is added or deleted, you need to click Search for Device again.
Otherwise, the system topology will not be updated.
Copyright © Huawei Digital Power Technologies Co., Ltd.