Huawei LUNA2000-97KWH-1H1 Maintenance Manual page 130

Smart string ess
Hide thumbs Also See for LUNA2000-97KWH-1H1:
Table of Contents

Advertisement

LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
Maintenance Manual
Fire
● If a fire occurs, power off the system if it is safe to do so.
● Extinguish the fire with carbon dioxide, FM-200 or ABC dry powder fire
extinguishers.
● Ask firefighters to avoid contact with high-voltage components during fire
fighting to prevent the risk of electric shock.
● Overheating may cause battery deformation, faults, and leakage of corrosive
electrolytes or toxic gases. Use respiratory protective equipment and keep a
safe distance from the batteries to prevent skin irritation and chemical burns.
Fire Alarm Horn/Strobe
When the alarm indicator on the equipment blinks or buzzes:
Gas Exhaust
Extinguishant Release or Fire
Issue 04 (2023-06-30)
D ANGER
Do not approach.
Do not open the door.
Stay away immediately.
Cut off the power supply remotely only when your safety is guaranteed.
Onsite personal protection: Do not directly face the exhaust vents.
Post-disaster product maintenance: Contact the Company's service engineers
for evaluation.
Suggestions for onsite O&M personnel:
a.
When a fire occurs, evacuate from the building or equipment area, press
the fire alarm bell, and immediately call the fire emergency service.
Notify the professional firefighters and provide them with relevant
product information, including but not limited to battery pack types, ESS
capacity, and battery pack location and distribution.
b.
Do not enter the affected building or equipment area under any
circumstances, and do not open the doors of the ESS. Isolate and monitor
the site. Keep irrelevant personnel away from the site.
c.
After calling the fire emergency service, remotely power off the system
(such as the Smart Transformer Station, Smart PCS, auxiliary power
supply devices, and combiner box power supply) while ensuring your own
safety.
d.
After professional firefighters arrive, provide relevant product
information, including but not limited to battery pack types, ESS capacity,
battery pack location and distribution, and user manuals.
e.
After the fire is extinguished, the site must be handled by professionals in
accordance with local laws and regulations. Do not open the doors of the
ESS without permission.
Copyright © Huawei Digital Power Technologies Co., Ltd.
28 Emergency Handling
124