LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
Maintenance Manual
Picture
●
●
●
●
●
●
Issue 04 (2023-06-30)
The storage environment requirements are as follows:
–
Ambient temperature: –40°C to +60°C (recommended: 20°C to 30°C)
–
Relative humidity: 5%–95% RH (recommended: about 45% RH)
–
Dry, clean, and well-ventilated
–
Away from corrosive organic solvents and gases
–
Away from direct sunlight
–
At least 2 meters away from heat sources
The batteries in storage must be disconnected from external devices. The
indicators (if any) on the batteries must be off.
The storage duration starts from the latest charge time labeled on the battery
package. If a battery is qualified after charge, update the latest charge time
(recommended format: YYYY-MM-DD HH:MM) and the next charge time
(Next charge time = Latest charge time + Charge interval) on the label.
The total storage and transportation time of the battery packs shall not
exceed eight months (starting from delivery). If it exceeds eight months,
charge the batteries and calibrate the SOC to at least 50%. Otherwise, the
battery performance and service life may be deteriorated.
Do not unpack batteries. If charging is necessary, they must be charged by
professionals as required and then returned to their original packaging after
charging.
The warehouse keeper shall collect battery storage information every month
and periodically report the battery inventory information. The batteries in
long-term storage shall be charged in a timely manner.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Keep dry: The package shall be kept
away from rain.
Stacking limit by number: The
packages shall not be vertically
stacked beyond the specified number.
The actual label may vary.
29 FAQ