1MRS756711 D
IEC 61850 name
.Op.general
LD0.FRPTUF1
.Op.general
LD0.FRPFRC1
.Op.general
2.3.1.26
Table 29:
LD0.FRPFRQ2 Frequency protection (2)
IEC 61850 name
LD0.FRPTRC2
.Str.general
LD0.FRPTOF2
.Op.general
LD0.FRPTUF2
.Op.general
LD0.FRPFRC2
.Op.general
2.3.1.27
Table 30:
LD0.FRPFRQ3 Frequency protection (3)
IEC 61850 name
LD0.FRPTRC3
.Str.general
LD0.FRPTOF3
.Op.general
LD0.FRPTUF3
.Op.general
LD0.FRPFRC3
.Op.general
2.3.1.28
Table 31:
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
IEC 61850 name
LD0.HAEFPTOC1
.Op.general
.Str.general
REF615
Point List Manual
SA name
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.FRPFRQ2 Frequency protection (2)
SA name
START
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.FRPFRQ3 Frequency protection (3)
SA name
START
OPR_OFRQ
OPR_UFRQ
OPR_FRG
LD0.HAEFPTOC1 Harmonics-based earth-fault protection
SA name
OPERATE
START
Description
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
Description
Stage operate
Stage start
Section 2
DNP3 data mappings
Values
1=Operate
1=Operate
1=Operate
Values
1=Start
1=Operate
1=Operate
1=Operate
Values
1=Start
1=Operate
1=Operate
1=Operate
Values
1=Operate
1=Start
23