Siemens 7ML5431 Operating Instructions Manual
Siemens 7ML5431 Operating Instructions Manual

Siemens 7ML5431 Operating Instructions Manual

Radar transmitters with ma/hart
Table of Contents

Advertisement

Quick Links

SITRANS LR250 with mA/HART
SITRANS L
Radar Transmitters
SITRANS LR250 with mA/HART
Operating Instructions
7ML5431 (LR250)
7ML5432 (LR250 flanged encapsulated antenna)
7ML5433 (LR250 hygienic encapsulated antenna)
10/2019
A5E32220602-AG
Introduction
Safety information
Description
Installing/mounting
Connecting
Commissioning
Remote operation
Parameter reference
Service and maintenance
Diagnosing and
troubleshooting
Technical data
Dimension drawings
Appendix A: Technical
reference
Appendix B: HART
communications
Appendix C: Certificates and
support
List of abbreviations
LCD menu structure
1
2
3
4
5
6
7
8
9
10
11
12
A
B
C
13
14

Advertisement

Table of Contents
loading

Summary of Contents for Siemens 7ML5431

  • Page 1 Diagnosing and troubleshooting Technical data Dimension drawings Appendix A: Technical reference Appendix B: HART communications Appendix C: Certificates and 7ML5431 (LR250) support 7ML5432 (LR250 flanged encapsulated antenna) 7ML5433 (LR250 hygienic encapsulated antenna) List of abbreviations LCD menu structure 10/2019 A5E32220602-AG...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Introduction........................... 9 LR250 mA/HART manual usage ..................9 Purpose of this documentation .................... 9 Revision history ......................... 10 Industrial use note ......................11 Checking the consignment ....................11 Security information ......................11 Transportation and storage ....................12 Notes on warranty ......................
  • Page 4 Table of contents 4.3.3 Orientation in a vessel with obstructions ................32 4.3.4 Mounting on a Stillpipe or Bypass Pipe ................32 4.3.5 Device orientation.......................33 Installation instructions .......................33 4.4.1 Threaded versions......................34 4.4.2 Flanged versions ........................35 4.4.3 Hygienic versions .......................37 Disassembly ........................38 Connecting ..........................39 Basic safety information .....................39 5.1.1 Condensation in the device ....................39...
  • Page 5 Table of contents 7.1.3.1 Configuring a new device ....................72 7.1.4 Quick Start Wizard via SIMATIC PDM ................72 7.1.5 Changing parameter settings using SIMATIC PDM ............76 7.1.6 Parameters accessed via pull-down menus ............... 77 7.1.6.1 Echo profile utilities ......................78 7.1.6.2 Echo profile ........................
  • Page 6 Table of contents Basic safety information ....................161 Cleaning ...........................161 Maintenance and repair work....................162 9.3.1 Unit repair and excluded liability ..................163 9.3.2 Part replacement ......................163 Disposal ...........................165 Return procedure ......................165 Diagnosing and troubleshooting ....................167 10.1 Communication troubleshooting ..................167 10.2 Device status icons ......................167 10.3 General fault codes ......................169 10.4...
  • Page 7 Table of contents 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851) ......206 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851) ....... 207 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1) ..... 208 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1) .....
  • Page 8 Table of contents A.5.2 Stainless steel horn antenna ....................246 A.5.3 Stainless steel flanged horn antenna ................247 A.5.4 PTFE flanged encapsulated antenna ................250 A.5.5 Aluminum horn, with polypropylene lens antenna version with polypropylene flange 3 inch/80 mm size only ......................251 A.5.6 PVDF antenna........................252 A.5.7 Hygienic encapsulated antenna ..................252...
  • Page 9: Introduction

    We always welcome suggestions and comments about manual content, design, and accessibility. Please direct your comments to: Technical publications (mailto:techpubs.smpi@siemens.com) Purpose of this documentation These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning.
  • Page 10: Revision History

    Introduction 1.3 Revision history Revision history This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware: Edition Firmware PDM EDD Date Changes rev. rev.
  • Page 11: Industrial Use Note

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 12: Transportation And Storage

    The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
  • Page 13: Safety Information

    Safety information Preconditions for safe use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device.
  • Page 14: Fcc Conformity

    Safety information 2.1 Preconditions for safe use 2.1.3 FCC Conformity US Installations only: Federal Communications Commission (FCC) rules Note • This device has been tested and found to comply with the limits Class B digital device part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 15: Conformity With European Directives

    Safety information 2.1 Preconditions for safe use Note • This device has been tested and found to comply with the limits RS- 211 - Level Probing Radar Equipment. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. •...
  • Page 16: Radio Equipment Directive (Red) 2014/53/Eu

    Safety information 2.1 Preconditions for safe use 2.1.6 Radio Equipment Directive (RED) 2014/53/EU For the receiver test that covers the influence of an interferer signal to the device, the performance criterion has at least the following level of performance according to ETSI TS 103 361 [6]: ●...
  • Page 17: Improper Device Modifications

    Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note...
  • Page 18 Safety information 2.4 Use in hazardous areas WARNING Loss of safety of device with type of protection "Intrinsic safety Ex i" If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas.
  • Page 19: Description

    Description SITRANS LR250 overview WARNING Loss of protection Danger to personnel, system and environment can result from improper use of the device. • SITRANS LR250 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired. SITRANS LR250 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries in storage vessels including high pressure and high temperature, to a range of 20 meters (66 feet).
  • Page 20: Programming

    This device is very easy to install and configure via a graphical local user interface (LUI). You can modify the built in parameters either locally via the Siemens infrared handheld programmer, or from a remote location using one of the following options: ●...
  • Page 21: Approvals And Certificates

    Description 3.4 Approvals and certificates Approvals and certificates Note For further details see Approvals (Page 180). SITRANS LR250 is available with approvals for General purpose, sanitary or hygienic and for hazardous areas. In all cases, check the nameplate on your device, and confirm the approval rating.
  • Page 22 Description 3.4 Approvals and certificates SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 23: Installing/Mounting

    Basic safety information Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 24: Unsuitable Cables, Cable Glands And/Or Plugs

    Installing/mounting 4.1 Basic safety information 4.1.1 Unsuitable cables, cable glands and/or plugs WARNING Unsuitable cables, cable glands and/or plugs Risk of explosion in hazardous areas. • Use only cable glands/plugs that comply with the requirements for the relevant type of protection.
  • Page 25: Pressure Equipment Directive, Ped, 14/68/Eu

    4.1.2.1 Pressure Equipment Directive, PED, 14/68/EU Siemens Level Transmitters with flanged, threaded, or sanitary clamp type process mounts have no pressure-bearing housing of their own and, therefore, do not come under the Pressure Equipment Directive as pressure or safety accessories (see EU Commission Guideline A-08 and A-20).
  • Page 26: Installation Location Requirements

    Installing/mounting 4.2 Installation location requirements Installation location requirements WARNING Aggressive atmospheres Danger to personnel, system and environment can result from unsuitable environment. • Provide an environment suitable to the housing rating and materials of construction. NOTICE Direct sunlight Device damage. The device can overheat or materials become brittle due to UV exposure.
  • Page 27 Installing/mounting 4.2 Installation location requirements ① Ambient temperature ② Device nameplate ③ Device tag ④ Process temperature (at process connection) ⑤ Process connection tag (contains process connection related information) Antenna ① ④ Horn -40 to +80 °C with FKM O-ring:-40 to +200 °C (-40 to (-40 to +176 °F) 392 °F) with FFKM O-ring:-20 to +200 °C (-4 to...
  • Page 28: Proper Mounting

    Installing/mounting 4.3 Proper mounting Proper mounting Note • Correct location is key to a successful application. • Avoid reflective interference from vessel walls and obstructions by following guidelines in this chapter. NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting.
  • Page 29: Nozzle Design

    Installing/mounting 4.3 Proper mounting 4.3.1 Nozzle design Threaded PVDF antenna Stainless steel horn antenna Polymeric lens versions Hygienic encapsulated antenna (HEA) ① Minimum clearance: 10 mm (0.4") ② Minimum diameter: 50 mm (2") ③ Maximum nozzle length ④ Maximum length/diameter ratio 1:1 ●...
  • Page 30: Nozzle Location

    Installing/mounting 4.3 Proper mounting 4.3.2 Nozzle location ● Avoid central locations on tall, narrow vessels ● Nozzle must be vertical and clear of imperfections Preferred Undesirable Beam angle Note • Beam width depends on antenna size and is approximate: see below. •...
  • Page 31 Installing/mounting 4.3 Proper mounting Emission cone type and beam angle Antenna type Antenna size Beam angle Horn 1.5" 19° 2" 15° 3" 10° 4" 8° Threaded PVDF 19° Process connection Process connection type size PTFE flanged encapsulated 2" Class 150 ASME B16.5 12.8°...
  • Page 32: Orientation In A Vessel With Obstructions

    Installing/mounting 4.3 Proper mounting 4.3.3 Orientation in a vessel with obstructions Polarization reference point For best results on a vessel with obstructions, or a stillpipe with openings, orient the front or back of the device toward the obstructions. For an illustration, see Device orientation (Page 33).
  • Page 33: Device Orientation

    Installing/mounting 4.4 Installation instructions 4.3.5 Device orientation Bypass pipe installation Stillpipe installation ① ① Vent Align front or back of device with stillpipe slots ② ② Align front or back of device with Slots vents Horn antenna version shown as example Installation instructions WARNING Pressure applications...
  • Page 34: Threaded Versions

    Installing/mounting 4.4 Installation instructions NOTICE Device handling Damage to device may result from improper handling. • Handle the device using the enclosure, not the process connection or tag, to avoid damage. • Take special care when handling the threaded PVDF and Hygienic or Flanged encapsulated antennas.
  • Page 35: Flanged Versions

    Installing/mounting 4.4 Installation instructions 4.4.2 Flanged versions NOTICE Improper materials The user is responsible for the selection of bolting and gasket materials (except for Flanged encapsulated antenna) which will fall within the limits of the process connection and its intended use, and which are suitable for the service conditions. Special Instructions for PTFE flanged encapsulated antenna only Note •...
  • Page 36 Installing/mounting 4.4 Installation instructions Flange bolting instructions: 1. Use cross-pattern sequence as shown. 2. Check uniformity of the flange gap. 3. Apply adjustments by selective tightening if required. 4. Torque incrementally until desired value is reached. 5. Check/re-torque after 4 to 6 hours. Recommendations for flange bolting: ●...
  • Page 37: Hygienic Versions

    Installing/mounting 4.4 Installation instructions 4.4.3 Hygienic versions WARNING Loss of sanitary approvals Loss of sanitary approvals can result from improper installation/mounting. • Take special care when installing in hygienic or sanitary applications. Comply with installation/mounting guidelines to ensure cleanliness and the ability to keep the wetted parts in a position to be readily cleanable.
  • Page 38: Disassembly

    Installing/mounting 4.5 Disassembly Disassembly DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. • Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure. WARNING Incorrect disassembly The following risks may result from incorrect disassembly: - Injury through electric shock - Risk through emerging media when connected to the process - Risk of explosion in hazardous area...
  • Page 39: Connecting

    Connecting Basic safety information 5.1.1 Condensation in the device NOTICE Condensation in the device Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). • Before taking the device into operation, let the device adapt for several hours in the new environment.
  • Page 40: Connecting Sitrans Lr250

    Connecting 5.2 Connecting SITRANS LR250 Connecting SITRANS LR250 WARNING Incorrect connection to power source Risk to personnel, system and environment can result from improper power connection. • The DC input terminals shall be supplied from a source providing electrical isolation between the input and output, in order to meet the applicable safety requirements of IEC 61010-1.
  • Page 41 Connecting 5.2 Connecting SITRANS LR250 ① Use a 2 mm Allen key to loosen the lid-lock set screw ④ Cable shield ② Plug (IP68) ⑤ Ground terminal ③ Optional cable gland (or NPT cable entry) a) b) May be shipped with the device. If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications.
  • Page 42: Wiring Setups For Hazardous Area Installations

    Connecting 5.3 Wiring setups for hazardous area installations Connecting HART Typical PLC/mA configuration with HART ① ④ Power supply Active PLC ② ⑤ SITRANS LR250 HART modem ③ ⑥ R = 250 Ω HART communicator Note • Depending on the system design, the power supply may be separate from the PLC, or integral to it.
  • Page 43: Intrinsically Safe Wiring

    Click on Certified Equipment then enter the certificate number IECEx SIR 05.0031X. Device nameplate (FM/CSA) ① Connection drawing number The FM/CSA Instrinsically Safe connection drawing number 23650653 listed on the nameplate can be downloaded from the Siemens Industry Image Database: SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 44: Non-Sparking Wiring

    5.3.2 Non-sparking wiring The ATEX certificate listed on the nameplate can be downloaded from our website: Product page (http://www.siemens.com/LR250) Go to: Support > Approvals / Certificates. ● For power demands see Curve 1 (General Purpose, Intrinsically Safe, Non- Sparking/Energy Limited, Non-incendive) (Page 257).
  • Page 45: Non-Incendive Wiring (Us/Canada Only)

    5.3 Wiring setups for hazardous area installations 5.3.3 Non-incendive wiring (US/Canada only) The FM/CSA Class 1, Div 2 connection drawing number 23650673 can be downloaded from the Siemens Industry Image Database: FM/CSA Class 1, Div 2 connection drawing number 23650673 (http://www.automation.siemens.com/bilddb/index.aspx?gridview=view2&objkey=G_FI01_XX _03551&showdetail=true&view=Search) ●...
  • Page 46: Increased Safety Wiring

    Increased safety wiring The ATEX certificate listed on the nameplate can be downloaded from our website: Product page (http://www.siemens.com/LR250) Go to Support > Approvals / Certificates. The IECEx certificate listed on the nameplate can be viewed on the IECEx website: IECEx (http://iecex.iec.ch/)
  • Page 47: Instructions Specific To Hazardous Area Installations

    Connecting 5.4 Instructions specific to hazardous area installations Instructions specific to hazardous area installations 5.4.1 (Reference European ATEX Directive 2014/34/EU) The following instructions apply to equipment covered by certificate number SIRA 06ATEX2358X, SIRA 08ATEX1301X, and SIRA 09ATEX4153X. 1. For use and assembly, refer to the main instructions. 2.
  • Page 48 Connecting 5.4 Instructions specific to hazardous area installations Special conditions for safe use (denoted by X after the certificate number) ● Parts of the enclosure may be non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam), which might cause a build-up of electrostatic charge on non-conducting surfaces.
  • Page 49: Commissioning

    Commissioning Basic safety information WARNING Loss of explosion protection Risk of explosion when device is not properly commissioned If opening device • Isolate from power. - or - • Ensure that the atmosphere is explosion-free (hot work permit). Ensure device is properly closed before returning to operation. Operating via the handheld programmer The handheld programmer used with this device contains lithium batteries that are non- replaceable.
  • Page 50: Power Up

    6.2.1 Power up Power up the device. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed. The first time the device is configured, you will be prompted to select a language (English, German, French, or Spanish).
  • Page 51: The Lcd Display

    Commissioning 6.2 Operating via the handheld programmer 6.2.2.1 The LCD display Measurement mode display Normal operation ① Toggle indicator for linear units or % ② Selected operation: level, space, distance, or volume ③ Measured value (level, space, distance, or volume) ④...
  • Page 52 Commissioning 6.2 Operating via the handheld programmer PROGRAM mode display Navigation view ① ④ Item band Current item number ② ⑤ Menu bar Current item ③ Current menu ● A visible menu bar indicates the menu list is too long to display all items. ●...
  • Page 53: Handheld Programmer (Part No. 7Ml1930-1Bk)

    Commissioning 6.2 Operating via the handheld programmer 6.2.2.2 Handheld programmer (Part No. 7ML1930-1BK) The programmer is ordered separately. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 54: Programming

    Commissioning 6.2 Operating via the handheld programmer Key functions in measurement mode Function Result Updates the loop current New value is displayed in LCD secondary region. Updates internal enclosure temperature reading Updates echo confidence value New value is displayed in LCD secondary region.
  • Page 55 Commissioning 6.2 Operating via the handheld programmer Parameter menus Note For the complete list of parameters with instructions, see Parameter Reference (Page 113). Parameters are identified by name and organized into function groups. See LCD menu structure (Page 267). 1. QUICK START 2.
  • Page 56 Commissioning 6.2 Operating via the handheld programmer Name Menu level Function UP or DOWN arrow menu or pa- Scroll to previous or next menu or param- rameter eter RIGHT arrow menu Go to first parameter in the selected menu, or open next menu. parameter Open Edit mode.
  • Page 57 Commissioning 6.2 Operating via the handheld programmer 4. Changing a numeric value ● Navigate to the desired parameter. ● Press RIGHT arrow to open parameter view. The current value is displayed. ● Press RIGHT arrow again to open Edit mode. The current value is highlighted. ●...
  • Page 58 Commissioning 6.2 Operating via the handheld programmer Key functions in edit mode Name Function UP or DOWN arrow Selecting Scrolls to item. options Numeric Increments or decrements digits • editing Toggles plus and minus sign • RIGHT arrow Selecting Accepts the data (writes the parame- •...
  • Page 59: Quick Start Wizard Via The Handheld Programmer

    Commissioning 6.2 Operating via the handheld programmer 6.2.3.1 Quick Start Wizard via the handheld programmer Note • A reset to factory defaults should be performed before running the Quick Start Wizard if the device has been used in a previous application. See Master Reset (4.1.). •...
  • Page 60 Commissioning 6.2 Operating via the handheld programmer Response Rate Sets the reaction speed of the device to measurement changes in the target range. Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Options Response Rate (1.3.) Fill rate per Minute (2.4.2.)/Empty rate per Minute (2.4.3.) SLOW...
  • Page 61 Commissioning 6.2 Operating via the handheld programmer ① ④ Space High Calibration Point (process full level) ② ⑤ Level Sensor reference point ③ ⑥ Distance Low Calibration Point (process empty level) The point from which High and Low Calibration points are referenced: see Dimension drawings.
  • Page 62: Auto False Echo Suppression

    Commissioning 6.2 Operating via the handheld programmer Wizard complete Options BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wiz menu when Quick Start is successfully completed.) Press DOWN arrow (Finish). Then press LEFT arrow to return to Measurement mode. SITRANS LR250 is now ready to operate. 6.2.3.2 Auto False Echo Suppression If you have a vessel with known obstructions, we recommend using Auto False Echo...
  • Page 63: Application Examples

    Commissioning 6.3 Application examples ● Use UP or DOWN arrow to scroll to an icon. When an icon is highlighted, that feature becomes active. ● To move a cross-hair, press RIGHT arrow to increase the value, LEFT arrow to decrease. ●...
  • Page 64 Commissioning 6.3 Application examples ① ⑤ Sensor reference point ② High calibration point ⑥ Low calibration point ③ 0.5 m ⑦ 0% level ④ 100% level Parameter type Parameter No. /Name Options/ Function Values Quick Start Introduction NEXT Continue with Wizard. Wizard parame- Language NEXT...
  • Page 65: Horizontal Vessel With Volume Measurement

    Commissioning 6.3 Application examples 6.3.2 Horizontal vessel with volume measurement Note The minimum distance from the flange face to the target is limited by Near Range (2.8.1.). To obtain level measurement/4 to 20 mA output proportional to vessel volume in a chemical vessel: ●...
  • Page 66: Application With Stillpipe

    Commissioning 6.3 Application examples Parameter type Parameter No./Name Options/ Function Values Quick Start Wiz- Introduction NEXT Continue with Wizard. ard parameters Language NEXT Continue with current language. Material LIQUID Response Rate Medium =1 m/minute Units meters Operation LEVEL Level is reported as Volume when a vessel shape is selected.
  • Page 67 Commissioning 6.3 Application examples ① ⑤ sensor reference point ② ⑥ high calibration point 50 mm I.D. ③ ⑦ 0.5 m low calibration point ④ vent hole Parameter type Parameter No./Name Options/Values Function Quick Start Wizard Introduction NEXT Continue with Wizard. Language NEXT Continue with current...
  • Page 68 Commissioning 6.3 Application examples Propagation Factor/Stillpipe Diameter ① ③ sensor reference point low calibration point ② ④ air gap CLEF range 2.8.4.4. 700 or 1000 mm (see CLEF Range settings in table below) Values Range 0.3 to 1.0 depending on pipe size Default 1.0000 Nominal Pipe Size...
  • Page 69: Remote Operation

    SIMATIC PDM is a software package used to commission and maintain process devices. Please consult the operating instructions or online help for details on using SIMATIC PDM. You can find more information on versions and compatibility at our website. See also SIMATIC PDM (www.siemens.com/simatic-pdm) 7.1.1 Functions in SIMATIC PDM Note •...
  • Page 70: Features Of Simatic Pdm Rev. 5.2, Sp1

    Check the support page of our website to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF): SIMATIC PDM Version (https://support.automation.siemens.com) Browse to Product Support > Automation Technology > Process control systems > SIMATIC PCS 7 > System components > Plant Device Management >...
  • Page 71: Deactivating Buffers

    Remote operation 7.1 Operating via SIMATIC PDM 7.1.2.1 Deactivating buffers This deactivation is required to align SIMATIC PDM with the HART modem for Windows 2000 and Windows XP operating Systems. Windows is a registered trademark of the ® ® ® Microsoft Corporation.
  • Page 72: Updating The Electronic Device Description (Edd)

    • Application Guides for setting up HART devices with SIMATIC PDM can be downloaded from our website: Product page (http://www.siemens.com/LR250). 1. Check that you have the most recent EDD, and if necessary update it. [See Updating the Electronic Device Description (EDD) (Page 72) above].
  • Page 73 Remote operation 7.1 Operating via SIMATIC PDM Quick start Note • A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application. See Master Reset via SIMATIC PDM (Page 85).
  • Page 74 Remote operation 7.1 Operating via SIMATIC PDM Step 1 – Identification Note • The layout of the dialog boxes shown may vary according to the resolution setting for your computer monitor. • SITRANS PDM limits the TAG field to a maximum of 24 characters. 1.
  • Page 75 Remote operation 7.1 Operating via SIMATIC PDM Step 3 – Vessel Shape The vessel shapes shown are prede- fined. For a vessel with obstructions, see Auto False Echo Suppression via SIMATIC PDM (Page 80). Select the vessel shape, and click on NEXT.
  • Page 76: Changing Parameter Settings Using Simatic Pdm

    Remote operation 7.1 Operating via SIMATIC PDM Step 4 – Ranges Set the parameters, and click on NEXT. Step 5 – Summary Check parameter settings, and click on BACK to return and revise values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and transfer them to the device.
  • Page 77: Parameters Accessed Via Pull-Down Menus

    Remote operation 7.1 Operating via SIMATIC PDM Many parameters are accessed via pull-down menus in PDM. See Parameters accessed via pull-down menus (Page 77) for others. 1. Launch SIMATIC PDM, connect to device, and upload data from device. 2. Adjust parameter values in the parameter value field then Enter. The status fields read Changed.
  • Page 78: Echo Profile Utilities

    Remote operation 7.1 Operating via SIMATIC PDM Device menus View menus Wizard - Quick Start (Page 72) Update Echo Profile Utilities (Page 78) Maintenance (Page 83) Wear (Page 86) Select Analog Output (Page 84) Self Test (Page 85) Loop Test (Page 85) Configuration Flag Reset (Page 85) Master Reset (Page 85) HART Communication (Page 86)
  • Page 79: View Saved Echo Profiles

    Remote operation 7.1 Operating via SIMATIC PDM ① Resolution ② Echo Profile Time Based Storage 7.1.6.3 View saved echo profiles To view a saved profile, click on the tab View Saved Echo Profiles. Echo profile data logging You can store up to 60 profiles at a selected interval (maximum 60 minutes). Inside Echo Profile Utilities, in the Echo Profile Time Based Storage window: ●...
  • Page 80: Auto False Echo Suppression

    Remote operation 7.1 Operating via SIMATIC PDM Open the menu Device – Echo Profile Utilities and click the tab TVT Shaper. ① ② Cursor ③ Echo profile ● Initial profile graph is blank upon entry to dialog. Click on Measure to view and upload the current TVT from device.
  • Page 81 Remote operation 7.1 Operating via SIMATIC PDM If you have a vessel with known obstructions, use Auto False Echo Suppression to prevent false echo detection. This feature can also be used if the device displays a false high level, or the reading is fluctuating between the correct level and a false high level. The device learns the echo profile over the whole measurement range and the TVT is shaped around all echoes present at that moment.
  • Page 82 Remote operation 7.1 Operating via SIMATIC PDM Before Auto False Echo Suppression ① ④ TVT Hover Level Echo marker ② ⑤ Default TVT Material level ③ False echo After Auto False Echo Suppression ① ④ False echo Material level ② ⑤...
  • Page 83: Echo Setup

    Remote operation 7.1 Operating via SIMATIC PDM 7.1.6.6 Echo setup Provides quick access to echo selection, filtering, and response rate parameters. Open the menu Device – Echo Profile Utilities and click on Echo Setup. 7.1.6.7 Maintenance You can set schedules and reminders for: ●...
  • Page 84: Select Analog Output

    Remote operation 7.1 Operating via SIMATIC PDM To set Device/Sensor Maintenance schedules: 1. Open the menu Device – Maintenance, and click on the Remaining Device/Sensor Lifetime tab. 2. Modify desired values, and if desired, set reminders for either or both of Reminder 1 before Lifetime (Required)/Reminder 2 before Lifetime (Demanded).
  • Page 85: Self Test

    Remote operation 7.1 Operating via SIMATIC PDM If a volume application is selected, mA Output is automatically set to Volume. See Analog Output (Page 241) for more details. 1. Open the menu Device – Select Analog Output. 2. Select Analog Output window displays the current setting: click OK. 3.
  • Page 86: Wear

    Remote operation 7.1 Operating via SIMATIC PDM Factory Defaults Factory Defaults resets all parameters to the default settings with the following exceptions: ● Device Address (5.1.) remains unchanged if the reset command is sent remotely (via AMS, PDM, DTM, FC375) but is reset to 0 if the reset command is sent via LUI. ●...
  • Page 87: Process Variables

    Remote operation 7.1 Operating via SIMATIC PDM 7.1.6.15 Process variables To compare outputs in real time open the menu View – Process Variables and click on Overview to see reading (level, space, distance, volume); analog output; device status; and current electronics temperature. To see highest and lowest electronics temperatures, navigate to Level Meter >...
  • Page 88: Trend

    Remote operation 7.1 Operating via SIMATIC PDM 7.1.6.16 Trend Open the menu View – Process Variables and click on Trend. Four trend lines can be monitored (distinguished by color in SIMATIC PDM): ① Space ② Distance ③ Level ④ Volume SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 89: Device Status

    Remote operation 7.1 Operating via SIMATIC PDM 7.1.6.17 Device status Open the menu View – Device Status to view Diagnostics, Device Status, Hardware/ Firmware (HW/FW) Status, and Maintenance status. ① update diagnostics In the Diagnostics window, click on Update diagnostics to update diagnostic information and refresh linked icons.
  • Page 90: Security

    Please consult the operating instructions or online help for details on using AMS Device Manager. You can find more information at: Emerson (http://www.emersonprocess.com/AMS/) Application Guides for setting up Siemens HART devices with AMS Device Manager are available on our website: SITRANS LR250 with mA/HART...
  • Page 91: Functions In Ams Device Manager

    The EDDs are linked to the type, version of configuration software, and protocol being used. Select the LR250 AMS EDD for the version of AMS installed. EDDs can be downloaded from our website, see Product page (http://www.siemens.com/LR250). The HART EDD for LR250 is labeled as supporting AMS Device Manager version 9.5. This EDD is also operational with AMS version 9.0 and 10.1.
  • Page 92: Configuring A New Device

    Configuring a new device 1. Check our website to make sure you have the most recent EDD. Product page (http://www.siemens.com/LR250) Go to Support > Software Downloads and if necessary download it. Save the files to your computer, and extract the zipped file to an easily accessed location.
  • Page 93: Pull-Down Menu Access

    Remote operation 7.2 Operating via AMS Device Manager Master reset Note Device Address (5.1.) remains unchanged if the reset command is sent remotely (via AMS, PDM, DTM, FC375) but is reset to 0 if the reset command is sent via HMI. ●...
  • Page 94: Quick Start Wizard Via Ams Device Manager

    Remote operation 7.2 Operating via AMS Device Manager ① Master reset 7.2.1.8 Quick Start Wizard via AMS Device Manager Note • A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application. See Master Reset (Page 92). •...
  • Page 95 Remote operation 7.2 Operating via AMS Device Manager Quick Start Step 1 – Identification 1. Navigate to Configure/Setup > Wizard > Quick Start. 2. Click on Step 1. 3. You can accept the default values without modification. (Description, Message, and Installation Date fields can be left blank.) If desired, make changes then click on Apply.
  • Page 96 Remote operation 7.2 Operating via AMS Device Manager 5. If a vessel shape with parabolic ends has been selected, set dimensions A and L. 6. Click on Apply. Step 5 – Summary Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device.
  • Page 97 Remote operation 7.2 Operating via AMS Device Manager 1. Click on the Breakpoints tab and enter values for level and volume for up to 32 breakpoints. 2. Navigate to Configure/Setup > Setup > Linearization and click on Characteristic to preview the characteristic curve of the vessel breakpoints. (The conversion will function correctly even if not all breakpoints are entered, but the curve will display correctly only if all breakpoints are entered.) 3.
  • Page 98 Remote operation 7.2 Operating via AMS Device Manager General ● Select Analog Output [see Select Analog Output (Page 84)] ● Master Reset [see Master Reset (Page 85)] Simulation/Test ● Self Test [see Self Test (Page 85)] ● Loop Test [see Loop Test (Page 85)] Setup Note For more detailed explanations of the parameters listed below see the pages referenced.
  • Page 99 Remote operation 7.2 Operating via AMS Device Manager Calibration [see Calibration (2.3.)] ● Low Calibration Point ● High Calibration Point ● Sensor Offset Rate [see Rate (2.4.)] ● Response Rate ● Fill Rate per Minute ● Empty Rate per Minute Fail-safe [see Fail-safe (2.5.)] ●...
  • Page 100 Remote operation 7.2 Operating via AMS Device Manager Signal Processing General Navigate to Configure/Setup > Setup > Signal Processing and click on General for access to: Range [see Signal Processing (2.8.)] ● Near Range ● Far Range ● Propagation Factor Echo Select [see Echo Select (2.8.4.)] ●...
  • Page 101 Remote operation 7.2 Operating via AMS Device Manager Modify the TVT to screen out false echoes. See Auto False Echo Suppression (2.8.7.1.) (Page 238). Navigate to Configure/Setup > Setup > Signal Processing and click on TVT. Click on one of the two tabs to access the parameters listed: TVT Setup [see TVT setup (2.8.7.)] ●...
  • Page 102: Maintenance And Diagnostics

    Remote operation 7.2 Operating via AMS Device Manager Local Display Navigate to Configure/Setup > Setup > Local Display for access to: ● Language ● LCD Fast Mode [see LCD Fast Mode (4.9.)] ● LCD Contrast [see LCD Contrast (4.10.)] 7.2.2 Maintenance and diagnostics Navigate to Maintenance and Diagnostics for access to: Remaining Device Lifetime [see Remaining Device Lifetime (4.2.)]...
  • Page 103: Communication

    Remote operation 7.2 Operating via AMS Device Manager Calibration Schedule [see Calibration Schedule (4.5.)] ● Calibration Interval ● Time Since Last Calibration ● Time Until Next Calibration ● Activation of Reminders ● Reminder 1 before Calibration (Required) ● Reminder 2 before Calibration (Demanded) Electronic Temperature ●...
  • Page 104: Device Diagnostics

    Remote operation 7.2 Operating via AMS Device Manager 7.2.5 Device Diagnostics Click on the Device Diagnostics bar at the bottom of the navigation window, for access to: Device Status Hardware/Firmware Status 7.2.5.1 Process variables To compare outputs in real time click on Process Variables at the bottom of the navigation window for access to: Process Variables ●...
  • Page 105: Password Protection

    Remote operation 7.2 Operating via AMS Device Manager Echo Profile 7.2.5.2 Password protection An AMS Device Manager administrator can configure the user to require a password. The use of passwords is recommended. A password should be assigned to the ’admin’ username immediately after installing AMS Device Manager.
  • Page 106 Remote operation 7.2 Operating via AMS Device Manager The Add User Wizard dialog allows you to: ● select a user type, standard (AMS Device Manager) or Window user. ● enter the username and password, and set permissions ● edit existing users SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 107: Ams Menu Structure

    Remote operation 7.2 Operating via AMS Device Manager 7.2.6 AMS menu structure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 108 Remote operation 7.2 Operating via AMS Device Manager SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 109 Remote operation 7.2 Operating via AMS Device Manager SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 110 Remote operation 7.2 Operating via AMS Device Manager SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 111: Operating Via Fdt (Field Device Tool)

    EDD but an EDD is independent of the operating system. 7.3.2 SITRANS DTM ● SITRANS DTM is an EDDL interpreter developed by Siemens to interpret the EDD for that device. ● To use SITRANS DTM to connect to a device, you must first install SITRANS DTM on your system and then install the device EDD written for SITRANS DTM.
  • Page 112: The Device Edd

    7.3 Operating via FDT (Field Device Tool) 7.3.3 The device EDD The SITRANS LR250 HART EDD for SITRANS DTM can be downloaded from our website: Product page (http://www.siemens.com/LR250). Go to Support > Software Downloads. 7.3.4 Configuring a new device via FDT The full process to configure a field device via FDT is outlined in an Application Guide which can be downloaded from our website under Support >...
  • Page 113: Parameter Reference

    Parameter reference Note • Parameter names and menu structure are almost identical for SIMATIC PDM and the local user interface (LUI). • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Mode toggles between PROGRAM and Measurement Modes. •...
  • Page 114 Parameter reference Quick Start Wizard (1.1.) From measurement screen, press RIGHT arrow twice to open the Quick Start Wizard menu. Select a wizard, press RIGHT arrow to open the first step, and follow the instructions. Note Do not use the Quick Start Wizard to modify individual parameters. (Perform customization only after the Quick Start has been completed.) ●...
  • Page 115 Parameter reference Sensor (2.2.) Units (2.2.1.) PV (Primary Value) and SV (Secondary Sensor measurement units). Used in setting High/Low Calibration Point, and displayed on LCD and in PDM. Values m, cm, mm, ft, in Default: m Sensor Mode (2.2.2.) ① ⑤...
  • Page 116 Parameter reference Material (2.2.3.) Automatically configures the device to operate in the chosen application type, by changing one or more of the following parameters: Propagation Factor (2.8.3.), Position Detect (2.8.4.2.), and/or CLEF Range (2.8.4.4.). Options LIQUID LIQUID LOW DK (low dielectric liquid - CLEF algorithm enabled) Related parameters Propagation Factor (2.8.3.) Position Detect (2.8.4.2.)
  • Page 117 Parameter reference High Calibration Pt. (2.3.2.) Distance from sensor reference point to High Calibration Point. Units are defined in Units (2.2.1.). Values Range: 0 to 20 m. Default 0.00 m Related parameters Units (2.2.1.) Near Range (2.8.1.) When setting the High Calibration Point value, note that echoes are ignored within Near Range (2.8.1.).
  • Page 118 Parameter reference Fill Rate per Minute (2.4.2.) Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows you to adjust the SITRANS LR250 response to decreases in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered. Options Range: 0 to 99999 m / min.
  • Page 119 Parameter reference Material Level (2.5.1.) Note The default setting depends whether your device is a standard or NAMUR NE 43-compliant device. Defines the mA output to use when the Fail-safe timer expires. STANDARD DEVICE Options 20.5 mA (max. mA Limit) 3.8 mA (min.
  • Page 120 Parameter reference Fail-Safe mA Value (2.5.3.) Note • The default settings are dependent on standard or NAMUR NE 43-compliant device. • Material Level (2.5.1.) must be set to VALUE to enable the Fail-Safe mA Value to be reported. Allows the user to define the mA value to be reported when the Fail-safe timer expires. Device Type STANDARD NAMUR NE43- COMPLIANT...
  • Page 121 Parameter reference Options Reference point Description Level Low Calibration Point measured as a percentage of the differ- ence between High Calibration Point and Space High Calibration Point Low Calibration Point Distance Sensor reference point measured as a percentage of Low Cali- bration Point Volume converts a level measurement to a volume output...
  • Page 122 Parameter reference Minimum mA limit (2.6.4.) Prevents the mA output from dropping below this minimum level for a measurement value. This does not restrict the Fail-safe or Manual settings. Values Range: 3.8 to 20.5 (mA) Default: 3.8 (mA) Maximum mA limit (2.6.5.) Prevents the mA output from rising above this maximum level for a measurement value.
  • Page 123 Parameter reference Vessel Shape (2.7.1.1.) Defines the vessel shape and allows the LR250 to calculate volume instead of level. If None is selected, no volume conversion is performed. Select the vessel shape matching the monitored vessel or reservoir. Vessel Shape LCD DISPLAY/ Description Also required None NONE/...
  • Page 124 Parameter reference Vessel Shape LCD DISPLAY/ Description Also required FLAT SLOPED BOT/ Maximum volume, Flat sloped bottom dimension A PARABOLIC ENDS/ Maximum volume, Parabolic end horizontal dimension A, dimension cylinder LINEAR TABLE / Linear- Maximum volume, ization table (level/volume tables 1-32 level and breakpoints) volume breakpoints Linearization Table must be selected in order for level/volume values [see Table 1-8 (2.7.2.)] to be...
  • Page 125 Parameter reference Vessel Dimension L (2.7.1.4.) Length of the cylindrical section of a horizontal parabolic end vessel. See Vessel Shape (2.7.1.1.) for an illustration. Values Range: 0.0 to 99.99 m Default: 0.0 Related Parameters Units (2.2.1.) Vessel Shape (2.7.1.1.) Table 1-8 (2.7.2.) Note Linearization Table must be selected in Vessel Shape (2.7.1.1.) in order for level/volume values to be transferred.
  • Page 126 Parameter reference Level 1 (2.7.2.1.) 1. Press RIGHT arrow to open Edit mode. 2. Enter level value and press RIGHT arrow to except it. 3. Press DOWN arrow to move to corresponding volume breakpoint. Volume 1 (2.7.2.2.) 1. Press RIGHT arrow to open Edit mode. 2.
  • Page 127 Parameter reference Signal Processing (2.8.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. Near Range (2.8.1.) The range in front of the device (measured from the sensor reference point) within which any echoes will be ignored.
  • Page 128 Parameter reference Propogation Factor (2.8.3.) Note • When operating in a stillpipe, values for CLEF Range (2.8.4.4.), and for the propagation factor, should be set according to the pipe size. See the table below. • For reliable results the antenna size must be close to the pipe size. Compensates for the change in microwave velocity due to propagation within a metal stillpipe instead of in free space.
  • Page 129 Parameter reference Echo Select (2.8.4.) Algorithm (2.8.4.1.) Selects the algorithm to be applied to the echo profile to extract the true echo. Options True First echo Largest echo Best of Largest and First echo Position Detect (2.8.4.2.) Defines where on the echo the distance measurement is determined. Options Center Hybrid (Center and CLEF)
  • Page 130 Parameter reference It is used from Low Calibration Point (process empty level ) up to the level defined by CLEF Range (see illustration below). Above that point the Center algorithm is used. For more detail see CLEF Range (Page 237). Values Range: 0 to 20 m (0 to 65.6 ft) Default: 0.0 m...
  • Page 131 Parameter reference Sampling Up (2.8.5.2.) Specifies the number of consecutive echoes that must appear above the echo currently selected, before the measurement is accepted as valid. Values Range: 1 to 50 Default: 5 Sampling Down (2.8.5.3.) Specifies the number of consecutive echoes that must appear below the echo currently selected, before the measurement is accepted as valid.
  • Page 132 Parameter reference TVT Setup (2.8.7.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. Auto False Echo Suppression (2.8.7.1.) Used together with Auto False Echo Suppression Range (2.8.7.2.) to screen out false echoes in a vessel with known obstructions. A ’learned TVT’ (time varying threshold) replaces the default TVT over a specified range.
  • Page 133 Parameter reference Before Auto False Echo Suppression ① ④ TVT Hover Level echo marker ② ⑤ default TVT material level ③ false echo 1. Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor reference point to the material surface using a rope or tape measure. 2.
  • Page 134 Parameter reference After Auto False Echo Suppression ① ④ false echo material level ② learned TVT ⑤ default TVT ③ Auto False Echo Suppression ⑥ echo marker Range To set Auto False Echo Suppression via SIMATIC PDM: Open the menu Device – Echo Profile Utilities and click on the tab Auto False Echo Suppression.
  • Page 135 Parameter reference Auto False Echo Suppression Range (2.8.7.2.) Note Changes take effect only at the next measurement. "Master reset" does not clear the learned/stored TVT, select "Off" to turn it off or "learn" for a new TVT. See Master Reset (4.1.) Specifies the range within which Learned TVT is used [see Auto False Echo Suppression (2.8.7.1.) for more detail].
  • Page 136 Parameter reference TVT shaper (2.8.8.) Note • The range is –100 to 100 bits. With 2 bits per dB this gives a range of –50 to 50 dB. • Shaper Mode (2.8.7.4.) must be turned ON in order for TVT shaper points to be transferred.
  • Page 137 Parameter reference Breakpoint 28-36 (2.8.8.4.) Values Range: –50 to 50 dB Default: 0 dB Breakpoint 37-40 (2.8.8.5.) Values Range: –50 to 50 dB Default: 0 dB Measured Values (2.8.9.) Read only. Allows you to view measured values for diagnostic purposes. To access measured values via SIMATIC PDM: Open the menu View –...
  • Page 138 Parameter reference Echo Profile (3.1.) Allows you to request the current echo profile either locally via the handheld programmer, or remotely via SIMATIC PDM, or AMS Device Manager. [For more detail see Echo Processing (Page 234)]. To request a profile via SIMATIC PDM: Open the menu Device –...
  • Page 139 Parameter reference Master Reset (4.1.) Note Following a reset to Factory Defaults, complete reprogramming is required. Resets all parameter to factory defaults, with the following exceptions: ● Device Address (5.1.) remains unchanged if the reset command is sent remotely (via AMS, PDM, DTM, FC375) but is reset to 0 if the reset command is sent via LUI.
  • Page 140 Parameter reference To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Remaining Device Lifetime tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ●...
  • Page 141 Parameter reference Time in Operation (4.2.2.) Read only. The amount of time the device has been operating. Remaining Lifetime (4.2.3.) Read only. Lifetime (Expected) (4.2.1.) less Time in Operation (4.2.2.). Activation of Reminders (4.2.4.) Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device –...
  • Page 142 Parameter reference Maintenance Status (4.2.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab, and check the Device Lifetime Status window. Acknowledge Status (4.2.8.) Indicates which level of maintenance reminder has been acknowledged. In SIMATIC PDM, open the menu View –...
  • Page 143 Parameter reference To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Remaining Sensor Lifetime tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ●...
  • Page 144 Parameter reference Time in Operation (4.3.2.) The amount of time the sensor has been operating. Can be reset to zero after performing a service or replacing the sensor. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Remaining Sensor Lifetime tab, and click on Sensor Replaced to restart the timer and clear any fault messages.
  • Page 145 Parameter reference Reminder 2 before Lifetime (Demanded) (4.3.6.) If Remaining Lifetime (4.3.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder. Values Range: 0 to Lifetime (Expected) (4.3.1.) Default: 0.019 years 1. Modify values as required. 2.
  • Page 146 Parameter reference Service Schedule (4.4.) Note • Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Maintenance/Service schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Device Lifetime (4.2.), Remaining Sensor Lifetime (4.3.), and Calibration Schedule (4.5.).
  • Page 147 Parameter reference Service Interval (4.4.1.) Note The device always operates in years. Changing the units affects only the parameter view of the Service Interval parameters in SIMATIC PDM. User-configurable recommended time between product inspections. Values Units : hours, days, years Range: 0 to 20 years Default: 1.0 year Units are selectable only via SIMATIC PDM.
  • Page 148 Parameter reference Activation of Reminders (4.4.4.) Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance. Allows you to enable a maintenance reminder. Options Timer OFF ON - no reminders checked ON - Reminder 1 (Maintenance Required) checked ON - Reminders 1 and 2 checked ON - Reminder 2 (Maintenance Demanded) checked...
  • Page 149 Parameter reference Acknowledge Status (4.4.8.) Indicates which level of maintenance reminder has been acknowledged. Open the menu View – Device Status, click on the Maintenance tab and check the Service Schedule Status window. Acknowledge (4.4.9.) Acknowledges the current maintenance reminder. To acknowledge a reminder via SIMATIC PDM: 1.
  • Page 150 Parameter reference Time Units Options Hours; days; years Default: years Selectable only via SIMATIC PDM. Calibration Interval (4.5.1.) Note The device always operates in years. Changing the units affects only the parameter view of Remaining Sensor Life parameters in SIMATIC PDM. User-configurable recommended time between product calibrations.
  • Page 151 Parameter reference Time Since Last Calibration (4.5.2.) Time elapsed since last calibration. Can be reset to zero after performing a calibration. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Calibration Schedule tab, and click on Calibration Performed to restart the timer and clear any fault messages.
  • Page 152 Parameter reference Reminder 2 before Calibration (Demanded) (4.5.6.) If Time Until Next Calibration (4.5.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder. Values Range: 0 to Calibration Interval (4.5.1.) Default: 0.164 years 1. Modify values as required. 2.
  • Page 153 Parameter reference Power-on Resets (4.8.) Read only. The number of power cycles that have occurred since manufacture. In SIMATIC PDM, open the menu Device – Wear. LCD Fast Mode (4.9.) Note • LCD Fast Mode takes effect only after 30 minutes of inactivity. (Each time the device is powered up, a further 30 minutes of inactivity is required.) •...
  • Page 154 Parameter reference Memory Test (4.12.) Allows verification of the RAM, EEPROM, and Flash memory of the SITRANS LR250. LCD Display IDLE No test in progress. BUSY Test in progress. PASS Memory test successful. FAIL Test failed. Err1 Test returned unexpected results. P Oxcafe Test passed with result data.
  • Page 155 Parameter reference Security (6.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. Remote Access (6.1.) Access Control (6.1.1.) Note If access control is changed to limit remote access, it can only be reset via the handheld programmer.
  • Page 156: Alphabetical Parameter List

    Parameter reference 8.1 Alphabetical parameter list PIN to Unlock (6.2.2.) Note • Do not lose your Unlock Value: it cannot be displayed once Write Protect (6.2.1.) has been set to a different value. • Valid only for operation via the handheld programmer. •...
  • Page 157 Parameter reference 8.1 Alphabetical parameter list Breakpoint 10-18 (2.8.8.2.) Breakpoint 19-27 (2.8.8.3.) Breakpoint 28-36 (2.8.8.4.) Breakpoint 37-40 (2.8.8.5.) Calibration (2.3.) CLEF Range (2.8.4.4.) Communication (5.) Confidence (2.8.6.1.) Current Internal Temperature (3.2.1.) Current Output Function (2.6.1.) Damping Filter (2.2.4.) Device (2.1.) Device Address (5.1.) Diagnostics (3.) Distance Measurement (2.8.9.3.)
  • Page 158 Parameter reference 8.1 Alphabetical parameter list Level 1 (2.7.2.1.) Level Measurement (2.8.9.1.) Linearization (2.7.) Loader Revision (2.1.3.) Local Access (6.2.) LOE Timer (2.5.2.) Low Calibration Pt. (2.3.1.) Lowest value (3.2.3.) mA Output Value (2.6.6.) Manufacture Date (4.6.) Master Reset (4.1.) Material (2.2.3.) Material Level (2.5.1.) Maximum mA limit (2.6.5.)
  • Page 159 Parameter reference 8.1 Alphabetical parameter list Shaper Mode (2.8.7.4.) Signal Processing (2.8.) Secondary Value (4.11.) Security (6.) Sensor (2.2.) Sensor Mode (2.2.2.) Sensor Offset (2.3.3.) Service (4.) Setup (2.) Space Measurement (2.8.9.2.) Table 1-8 (2.7.2.) Table 9-16 (2.7.3.) Table 17-24 (2.7.4.) Table 25-32 (2.7.5.) TVT Setup (2.8.7.) TVT Shaper (2.8.8.)
  • Page 160 Parameter reference 8.1 Alphabetical parameter list SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 161: Service And Maintenance

    Service and maintenance Basic safety information WARNING Impermissible repair of the device • Repair must be carried out by Siemens authorized personnel only. CAUTION Releasing button lock Improper modification of parameters could influence process safety. • Make sure that only authorized personnel may cancel the button locking of devices for safety-related applications.
  • Page 162: Maintenance And Repair Work

    Service and maintenance 9.3 Maintenance and repair work WARNING Electrostatic charge Danger of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic surfaces with a dry cloth. • Prevent electrostatic charging in hazardous areas. Maintenance and repair work The device is maintenance-free.
  • Page 163: Unit Repair And Excluded Liability

    Replacing the antenna Changing to a different antenna type may be performed by a Siemens authorized repair center or personnel. If the electronics or enclosure require replacement due to damage or failure, please ensure the correct antenna version is used, otherwise a re-calibration will need to be performed by Siemens authorized personnel.
  • Page 164 Tuchenhagen, Hygienic encapsulated antenna Lens and silicon Type F A5E32572794 O-ring Type N A5E32572795 Note For more information about accessories such as clamps, seals and process connections, please see the catalog on the product page (http://www.siemens.com/LR250) (http://www.siemens.com/LR250). SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 165: Disposal

    – Number of returned devices/replacement parts – Reason for returning the item(s) ● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."...
  • Page 166 Service and maintenance 9.5 Return procedure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 167: Diagnosing And Troubleshooting

    Try pressing Mode to put the device into PROGRAM mode. If you continue to experience problems go to our website and check the FAQs for SITRANS LR250: Product page (http://www.siemens.com/LR250), or contact your Siemens representative. 10.2 Device status icons Icon Priority...
  • Page 168 Diagnosing and troubleshooting 10.2 Device status icons Icon Priority Meaning Level Maintenance required • Measured signal still valid • Process value has reached an alarm limit • Process value has reached a warning limit • Process value has reached a tolerance limit •...
  • Page 169: General Fault Codes

    Adjust process conditions to minimize foam or other tions, invalid configuration range. • adverse conditions. Correct configuration range. • If fault persists, contact your local Siemens repre- • sentative. S: 2 Unable to collect profile because of a power Repair required: contact your local Siemens representa- condition that is outside the operating range of tive.
  • Page 170 S: 34 Factory calibration for the device has been lost. Repair required: contact your local Siemens representa- tive S: 35 Factory calibration for the device has been lost. Repair required: contact your local Siemens representa-...
  • Page 171 • conditions, invalid calibration range. If fault persists, or for 1 and 2, contact your local Siemens representative. S: 53 Configuration lost: one or more parameter Restore user parameters using SIMATIC PDM.
  • Page 172: Operation Troubleshooting

    Diagnosing and troubleshooting 10.4 Operation troubleshooting 10.4 Operation troubleshooting Operating symptoms, probable causes, and resolutions. Symptom Cause Action Display shows level or target is out of range check specifications • check Low Calibration Pt. (2.3.1.) • increase Confidence (2.8.6.1.) • Display shows material build-up on antenna clean the antenna...
  • Page 173 Diagnosing and troubleshooting 10.4 Operation troubleshooting Symptom Cause Action liquid surface vortexed decrease Fill Rate per Minute (2.4.2.) • relocate device to side pipe • increase confidence threshold in Echo Threshold (2.8.4.3.) • material filling Re-locate SITRANS LR250 • Reading response Fill Rate per Minute (2.4.2.) set- increase measurement response if possible •...
  • Page 174 Diagnosing and troubleshooting 10.4 Operation troubleshooting SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 175: Technical Data

    Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power General Purpose Intrinsically Safe Nominal 24 V DC at 550 Ohm Non-Sparking...
  • Page 176 Technical data 11.2 Performance Measurement Accuracy (measured in accordance with IEC 60770-1) Maximum measured error = 3 mm (0.12") including hysteresis and non- 1) 2) 3) repeatability Frequency K-band Maximum measurement range 1.5" antenna 10 m (32.8 ft) 2" threaded PVDF antenna 2"/DN50/50A Flanged encapsulated antenna (FEA) 2"...
  • Page 177: Interface

    Max. line length multi-wire: ≤ 1500 m (4921 ft) Protocol HART, Version 5.1 Configuration Remote Siemens SIMATIC PDM or AMS Device Manager (PC) Local Siemens infrared handheld programmer, or HART handheld communicator Display (local) graphic LCD, with bar graph representing level See A.6.3 for details on version exclusions...
  • Page 178 Technical data 11.4 Mechanical Wetted materials 1600 PTFE lens PTFE hygenic Hygienic encapsulated antenna ISO 2852 (2, 3, 4")DIN 11851 (DN50, DN80, encapsulated (HEA) connection DN100)DIN 11864-1/2/3 (DN50, DN80, DN100)Tuchenhagen (Type F [50 mm] and Type N [68 mm])316L /1.4404 or 316L /1.4435 stainless steel Wetted materials 316L /1.4404 or 316L /1.4435 stainless steel...
  • Page 179: Environmental

    Technical data 11.5 Environmental 150 A JIS 10K approximately 16.3 kg (35.9 lb) 2" ISO2852 HEA approximately 4.7 kg (10.4 lb) 3" ISO2852 HEA approximately 6.3 kg (13.9 lb) 4" ISO2852 HEA approximately 6.8 kg (15 lb) DN50 DIN 11864-1 HEA approximately 4.8 kg (10.6 lb) DN80 DIN 11864-1 HEA approximately 6.7 kg (14.8 lb)
  • Page 180: Process

    Technical data 11.6 Process 11.6 Process Note The maximum temperature is dependent on the process connection, antenna materials, and vessel pressure. For more detailed information see Maximum Process Temperature Chart (Page 244) and Process Pressure/Temperature derating curves (Page 245). Temperature at process con- Stainless steel an- with FKM O- −40 to +200 °C (−40 to +392 °F)
  • Page 181 Technical data 11.7 Approvals Application type LR250 version Approval rating Valid for: FM/CSA US/Canada Class I, Div. 1, Groups A, B, C, D Class II, Div. 1, Groups E, F, G Class III T4 INMETRO: DNV 12.0087 X Brazil Ex ia IIC T4 Ga Ex ia ta IIIC T100 °C Da IP67/IP68 -40 °C ≤...
  • Page 182: Programmer (Infrared Keypad)

    Year 2014: Alpha code = E Year 2020: Alpha code = M Year 2015: Alpha code = F Siemens Milltronics Infrared IS (Intrinsically Safe) Handheld Programmer for hazardous and all other locations (battery is non-replaceable). Approvals FM/CSA Class I, II, III, Div. 1, Gr. A to G T6 ATEX 1 GD Ex ia op is IIC T4 Ga Ex ia op is IIIC T135°C Da...
  • Page 183: Dimension Drawings

    Dimension drawings 12.1 Universal polymeric flange ① Bolt hole circle max. diameter ② Bolt hole circle min. diameter ③ Bolt hole ④ Flange O.D. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 184 Dimension drawings 12.1 Universal polymeric flange Nominal pipe Flange O.D. Thickness Bolt hole Bolt hole Bolt hole No. of size circle max. ∅ circle min. Ø radius slotted holes 3 (80) 7.87 (200) 0.7 (17.5) 6.30 (160) 5.91 (150) 0.37 (9.5) 4 (100) 9.00 (229) 0.7 (17.5)
  • Page 185: Aluminum Horn Antenna

    Dimension drawings 12.2 Aluminum horn antenna 12.2 Aluminum horn antenna ① ½" NPT or M20 cable entry ② threaded cover ③ process connection tag ④ Aluminum horn antenna Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 186: Mounting Bracket

    Dimension drawings 12.3 Mounting bracket 12.3 Mounting bracket ① Stainless steel socket head screw (4) M5 x 0.8 x 14 screws, washers, lock washers ② Mounting bracket ③ (2) M5 x 0.8 x 16 screws, washers, lock washers SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 187 Dimension drawings 12.3 Mounting bracket ④ (2) M5 x 0.8 x 16 screws, washers, lock washers, nylon insert lock nuts Dimensions in mm (inch) Note Torque the bracket screws to 5 Nm (3.7ft/lbs) to hold the aiming adjustment of the antenna. Wall and ceiling mount for free space applications SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 188: Aluminum Horn With Polypropylene Lens Antenna And Polymeric Flange

    Dimension drawings 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange 12.4 Aluminum horn with polypropylene lens antenna and polymeric flange ① ½" NPT or M20 cable entry ② threaded cover ③ process connection tag ④ aluminum horn with polypropylene lens antenna Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 189: Stainless Steel Threaded Horn Antenna

    Reference drawing listed on the tag is available for download from our website under Support/Installation drawings/Level Measurement/Continuous - Radar/LR250: Product page (http://www.siemens.com/LR250) • Process connection drawings are also available for download from the Installation Drawings page. • Signal amplitude increases with horn diameter, so use the largest practical size.
  • Page 190 Dimension drawings 12.5 Stainless steel threaded horn antenna ① ⑦ ½" NPT cable entry, or M20 cable gland enclosure/electronics ② ⑧ threaded cover retaining collar ③ ⑨ 2" horn process connection tag ④ ⑩ 3" horn horn ⑤ ⑪ 4" horn sensor reference point ⑥...
  • Page 191 Dimension drawings 12.5 Stainless steel threaded horn antenna Height from bottom of horn to sensor reference point as shown: see dimension drawing. -3dB in the direction of the polarization axis. For an illustration, see Polarization reference point (Page 32). SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 192: Stainless Steel Threaded Horn Antenna With Extension

    Dimension drawings 12.6 Stainless steel threaded horn antenna with extension 12.6 Stainless steel threaded horn antenna with extension ① ⑦ ½" NPT cable entry, or M20 cable gland enclosure/electronics ② ⑧ threaded cover retaining collar ③ ⑨ 2" horn process connection tag ④...
  • Page 193 Dimension drawings 12.6 Stainless steel threaded horn antenna with extension Threaded horn with extension dimensions Antenna Antenna Height to sensor reference point, mm (inch) Beam Angle Measurement Type O.D., mm (°) range, m (ft) 1-1/2" threaded con- 2" threaded con- 3"...
  • Page 194: Stainless Steel Flanged Horn Antenna

    Dimension drawings 12.7 Stainless steel flanged horn antenna 12.7 Stainless steel flanged horn antenna ① ⑥ ½" NPT cable entry, or M20 cable gland flange ② ⑦ threaded cover name-plate ③ ⑧ horn retaining collar ④ ⑨ horn O.D. process connection tag ⑤...
  • Page 195 Dimension drawings 12.7 Stainless steel flanged horn antenna Height from bottom of horn to sensor reference point as shown: see Stainless steel flanged horn antenna with extension (Page 196). See also Raised-Face flange (Page 221), or Flat- Face flange (Page 226). -3dB in the direction of the polarization axis (see Polarization reference point (Page 32) for an illustration).
  • Page 196: Stainless Steel Flanged Horn Antenna With Extension

    Dimension drawings 12.8 Stainless steel flanged horn antenna with extension 12.8 Stainless steel flanged horn antenna with extension ① ⑥ ½" NPT cable entry, or M20 cable gland flange ② ⑦ threaded cover name-plate ③ ⑧ horn retaining collar ④ ⑨...
  • Page 197 Dimension drawings 12.8 Stainless steel flanged horn antenna with extension Flanged horn with extension dimensions Nominal horn Horn O.D., mm Height to sensor reference point , mm (inch) Beam angle Measurement range, size, (inch) (°) m (ft) mm (inch) Stainless steel flange: Optional alloy raised or flat-face flange...
  • Page 198: Ptfe Flanged Encapsulated Antenna (2"/Dn50/50A Sizes Only)

    Dimension drawings 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only) 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only) ① ⑥ ½" NPT cable entry, or M20 cable gland flange ② ⑦ threaded cover see table below ③ ⑧ see table below see table below ④...
  • Page 199 Dimension drawings 12.9 PTFE Flanged encapsulated antenna (2"/DN50/50A sizes only) Flanged encapsulated antenna (2"/DN50/50A) dimensions ③ ⑦ ⑧ ⑩ Flange size mm (inch) mm (inch) mm (inch) mm (inch) 2"/DN50/50A 263 (10.35) 223 (8.78) 274 (10.79) 11 (0.43) Height from tip of lens to sensor reference point as shown. Flange size Flange class Flange O.D.
  • Page 200: Ptfe Flanged Encapsulated Antenna (3"/Dn80/80A Sizes And Larger)

    Dimension drawings 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger) 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger) ① ⑥ ½" NPT cable entry, or M20 cable gland retaining collar ② ⑦ threaded cover see table below ③ ⑧...
  • Page 201 Dimension drawings 12.10 PTFE Flanged encapsulated antenna (3"/DN80/80A sizes and larger) Flanged encapsulated antenna (3"/DN80/80A and larger) dimensions ③ ⑦ ⑧ ⑩ Flange size mm (inch) mm (inch) mm (inch) mm (inch) 3"/DN80/80A 328 (12.91) 288 (11.34) 343 (13.50) 15 (0.59) 4"/DN100/100A 328 (12.91) 288 (11.34)
  • Page 202: Hygienic Encapsulated Antenna (2" Iso 2852 Sanitary Clamp)

    Dimension drawings 12.11 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp) 12.11 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp) Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 203: Hygienic Encapsulated Antenna (3" Iso 2852 Sanitary Clamp)

    Dimension drawings 12.12 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp) 12.12 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp) Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 204: Hygienic Encapsulated Antenna (4" Iso 2852 Sanitary Clamp)

    Dimension drawings 12.13 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp) 12.13 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp) Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 205: Hygienic Encapsulated Antenna (Dn50 Nozzle/Slotted Nut To Din 11851)

    Dimension drawings 12.14 Hygienic encapsulated antenna (DN50 nozzle/slotted nut to DIN 11851) 12.14 Hygienic encapsulated antenna (DN50 nozzle/slotted nut to DIN 11851) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 206: Hygienic Encapsulated Antenna (Dn80 Nozzle/Slotted Nut To Din 11851)

    Dimension drawings 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851) 12.15 Hygienic encapsulated antenna (DN80 nozzle/slotted nut to DIN 11851) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 207: Hygienic Encapsulated Antenna (Dn100 Nozzle/Slotted Nut To Din 11851)

    Dimension drawings 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851) 12.16 Hygienic encapsulated antenna (DN100 nozzle/slotted nut to DIN 11851) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 208: Hygienic Encapsulated Antenna (Dn50 Aseptic Slotted Nut To Din 11864-1)

    Dimension drawings 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1) 12.17 Hygienic encapsulated antenna (DN50 aseptic slotted nut to DIN 11864-1) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 209: Hygienic Encapsulated Antenna (Dn80 Aseptic Slotted Nut To Din 11864-1)

    Dimension drawings 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1) 12.18 Hygienic encapsulated antenna (DN80 aseptic slotted nut to DIN 11864-1) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 210: Hygienic Encapsulated Antenna (Dn100 Aseptic Slotted Nut To Din 11864-1)

    Dimension drawings 12.19 Hygienic encapsulated antenna (DN100 aseptic slotted nut to DIN 11864-1) 12.19 Hygienic encapsulated antenna (DN100 aseptic slotted nut to DIN 11864-1) Dimensions in mm (inch) Note Cut out of process connection and placement of threaded nut are shown for illustration purposes only.
  • Page 211: Hygienic Encapsulated Antenna (Dn50 Aseptic Flange To Din 11864-2)

    Dimension drawings 12.20 Hygienic encapsulated antenna (DN50 aseptic flange to DIN 11864-2) 12.20 Hygienic encapsulated antenna (DN50 aseptic flange to DIN 11864- Dimensions in mm (inch) Note Cut out of process connection and flange are shown for illustration purposes only. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 212: Hygienic Encapsulated Antenna (Dn80 Aseptic Flange To Din 11864-2)

    Dimension drawings 12.21 Hygienic encapsulated antenna (DN80 aseptic flange to DIN 11864-2) 12.21 Hygienic encapsulated antenna (DN80 aseptic flange to DIN 11864- Dimensions in mm (inch) Note Cut out of process connection and flange are shown for illustration purposes only. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 213: Hygienic Encapsulated Antenna (Dn100 Aseptic Flange To Din 11864-2)

    Dimension drawings 12.22 Hygienic encapsulated antenna (DN100 aseptic flange to DIN 11864-2) 12.22 Hygienic encapsulated antenna (DN100 aseptic flange to DIN 11864-2) Dimensions in mm (inch) Note The cut out of the process connection and the flange are shown for illustration purposes only.
  • Page 214: Hygienic Encapsulated Antenna (Dn50 Aseptic Clamp To Din 11864-3)

    Dimension drawings 12.23 Hygienic encapsulated antenna (DN50 aseptic clamp to DIN 11864-3) 12.23 Hygienic encapsulated antenna (DN50 aseptic clamp to DIN 11864- Dimensions in mm (inch) Note Cut out of process connection is shown for illustration purposes only. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 215: Hygienic Encapsulated Antenna (Dn80 Aseptic Clamp To Din 11864-3)

    Dimension drawings 12.24 Hygienic encapsulated antenna (DN80 aseptic clamp to DIN 11864-3) 12.24 Hygienic encapsulated antenna (DN80 aseptic clamp to DIN 11864- Dimensions in mm (inch) Note Cut out of process connection is shown for illustration purposes only. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 216: Hygienic Encapsulated Antenna (Dn100 Aseptic Clamp To Din 11864-3)

    Dimension drawings 12.25 Hygienic encapsulated antenna (DN100 aseptic clamp to DIN 11864-3) 12.25 Hygienic encapsulated antenna (DN100 aseptic clamp to DIN 11864-3) Dimensions in mm (inch) Note Cut out of process connection is shown for illustration purposes only. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 217: Hygienic Encapsulated Antenna (Tuchenhagen Type N)

    Dimension drawings 12.26 Hygienic encapsulated antenna (Tuchenhagen Type N) 12.26 Hygienic encapsulated antenna (Tuchenhagen Type N) Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 218: Hygienic Encapsulated Antenna (Tuchenhagen Type F)

    Dimension drawings 12.27 Hygienic encapsulated antenna (Tuchenhagen Type F) 12.27 Hygienic encapsulated antenna (Tuchenhagen Type F) Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 219: Threaded Pvdf Antenna

    Dimension drawings 12.28 Threaded PVDF antenna 12.28 Threaded PVDF antenna SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 220: Threaded Connection Markings

    Dimension drawings 12.29 Threaded connection markings Threaded PVDF antenna dimensions Nominal antenna Antenna O.D. Height to sensor Beam angle Measurement size reference point range 50 mm (2") 49.5 mm (1.94") 121 mm (4.76") 19 degrees 10 m (32.8 ft) Height from bottom of antenna to sensor reference point as shown: see dimension drawing.
  • Page 221: Raised-Face Flange

    Dimension drawings 12.30 Raised-Face flange 12.30 Raised-Face flange Stainless steel or optional alloy N06022/2.4602 (Hastelloy C-22) ® ① ⑥ angle of adjacent bolt holes bolt hole circle diameter ② ⑦ bolt hole diameter facing height ③ ⑧ bolt hole circle diameter facing diameter ④...
  • Page 222 Dimension drawings 12.30 Raised-Face flange Raised-Face flange dimensions ⑤ ③ ② ① ⑧ ⑩ Pipe size Flange bolt No. of bolts hole pattern Flange Bolt hole Bolt hole Ø Angle of Facing Ø Thickness O.D. circle Ø (mm) adjacent (mm) (mm) (mm) (mm)
  • Page 223 Serial number: a unique number allotted to each flange, including the date of manufacture (MMDDYY) followed by a number from 001 to 999 (indicating the sequential unit produced). Flange series: the Siemens Milltronics drawing identification. Heat code: a flange material batch code identification.
  • Page 224: Raised-Face Flange Per En 1092-1 For Flanged Encapsulated Antenna

    Dimension drawings 12.31 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna 12.31 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna Stainless steel ① ⑤ angle of adjacent bolt holes flange O.D. ② ⑥ bolt hole diameter facing height ③...
  • Page 225 Serial number: a unique number allotted to each flange, including the date of manufacture (MMDDYY) followed by a number from 001 to 999 (indicating the sequential unit produced). Flange series: the Siemens Milltronics drawing identification. Heat code: a flange material batch code identification.
  • Page 226: Flat-Face Flange

    Dimension drawings 12.32 Flat-Face flange 12.32 Flat-Face flange SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 227 Serial number: A unique number allotted to each flange, including the date of manufacture (MMDDYY) followed by a number from 001 to 999 (indicating the sequential unit produced). Flange series: The Siemens Milltronics drawing identification. Nominal size: The flange size followed by the hole pattern for a particular flange class. For example: •...
  • Page 228: Aseptic/Hygienic Flange Dn50, Dn80, Dn100 For Din 11864-2

    Dimension drawings 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2 Aseptic/hygienic flange DN50 Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 229 Dimension drawings 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2 Aseptic/hygienic flange DN80 Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 230 Dimension drawings 12.33 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2 Aseptic/hygienic flange DN100 Dimensions in mm (inch) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 231: Process Connection Tag (Pressure Rated Versions)

    Dimension drawings 12.34 Process connection tag (pressure rated versions) 12.34 Process connection tag (pressure rated versions) For pressure-rated versions only, the process connection label lists the following information: Process connection tag (pressure rated versions) Item Sample Text Comments/Explanation SERIAL # GYZ / 00000000 Pressure Boundary Assembly NOMINAL PIPE SIZE (DN)
  • Page 232 Dimension drawings 12.34 Process connection tag (pressure rated versions) SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 233: Appendix A: Technical Reference

    Appendix A: Technical reference Note Where a number follows the parameter name [for example, Master Reset (4.1.)] this is the parameter access number via the handheld programmer. See Parameter Reference (Page 113) for a complete list of parameters. Principles of operation SITRANS LR250 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries.
  • Page 234: Echo Processing

    Echo Processing A.2.1 Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
  • Page 235 Appendix A: Technical reference A.2 Echo Processing ① default TVT ② echo profile ③ material level ④ echo marker The device characterizes all echoes that rise above the TVT as potential good echoes. Each peak is assigned a rating based on its strength, area, height above the TVT, and reliability, amongst other characteristics.
  • Page 236 Appendix A: Technical reference A.2 Echo Processing Hybrid Uses the Center algorithm for the top part of the vessel, and the CLEF algorithm for the part nearest the vessel bottom, according to the setting for CLEF range. CLEF (Constrained Leading Edge Fit) ●...
  • Page 237: Clef Range

    Appendix A: Technical reference A.2 Echo Processing ① default TVT ② material echo selected ③ vessel bottom echo ④ echo marker A.2.3 CLEF Range CLEF Range (2.8.4.4.) is referenced from Low Calibration Point (process empty level ). When the Hybrid algorithm is selected in Position Detect (2.8.4.2.), the CLEF algorithm will be applied up to the limit of CLEF Range.
  • Page 238: Echo Lock

    Appendix A: Technical reference A.2 Echo Processing A.2.5 Echo Lock If the echo selected by Algorithm is within the Echo Lock window, the window is centered about the echo, which is used to derive the measurement. In radar applications, two measurement verification options are used with Echo Lock (2.8.5.1.): Lock Off SITRANS LR250 responds immediately to a new selected echo (within the restrictions set by...
  • Page 239 Appendix A: Technical reference A.2 Echo Processing Example before Auto False Echo Suppression ① ⑤ default TVT high calibration point = 0 ② ⑥ false echo obstruction at 1.3. m ③ ⑦ material echo material level at 3.2 m ④ sensor reference point Example after Auto False Echo Suppression Auto False Echo...
  • Page 240: Measurement Range

    Appendix A: Technical reference A.2 Echo Processing A.2.7 Measurement Range Near Range (2.8.1.) Near Range programs SITRANS LR250 to ignore the zone in front of the antenna. The default blanking distance is 50 mm (1.97") from the end of the antenna. Near Range allows you to increase the blanking value from its factory default.
  • Page 241: Damping

    Appendix A: Technical reference A.3 Analog Output A.2.9 Damping Damping Filter (2.2.4.) smooths out the response to a sudden change in level. This is an exponential filter and the engineering unit is always in seconds. In 5 time constants the output rises exponentially: from 63.2% of the change in the first time constant, to almost 100% of the change by the end of the 5th time constant.
  • Page 242: Sensor Mode

    Appendix A: Technical reference A.3 Analog Output A.3.1 Sensor Mode This parameter controls the input. Depending on the reference point used, the measurement reports either Level, Space, or Distance. By default Sensor Mode is set to Level. Operation Description Reference point NO SERVICE Measurement and associated loop current not being updated.
  • Page 243: Loss Of Echo (Loe)

    Appendix A: Technical reference A.3 Analog Output A.3.3 Loss of Echo (LOE) A loss of echo (LOE) occurs when the calculated measurement is judged to be unreliable because the echo confidence value has dropped below the echo confidence threshold. Confidence (2.8.6.1.) describes the quality of an echo. Higher values represent higher quality.
  • Page 244: Maximum Process Temperature Chart

    Appendix A: Technical reference A.4 Maximum Process Temperature Chart Maximum Process Temperature Chart WARNING Exceeded maximum internal and process temperatures Danger of device malfunction • Internal temperature must not exceed +80 ° C (+176 °F). • Process temperature must not exceed limits specified by the antenna type. Note •...
  • Page 245: Process Pressure/Temperature Derating Curves

    Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 246: Pressure Equipment Directive, Ped, 14/68/Eu

    A.5.1 Pressure Equipment Directive, PED, 14/68/EU Siemens Level Transmitters with flanged, threaded, or sanitary clamp type process mounts have no pressure-bearing housing of their own and, therefore, do not come under the Pressure Equipment Directive as pressure or safety accessories (see EU Commission Guideline A-08 and A-20).
  • Page 247: Stainless Steel Flanged Horn Antenna

    Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves A.5.3 Stainless steel flanged horn antenna JIS B 2220, 10K: 50A, 80A, and 100A ① Atmospheric Allowable operating pressures Allowable operating temperatures EN1092-1, PN16: DN50, DN80, DN100, and DN150 SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 248 Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves ① Atmospheric Allowable operating pressures Allowable operating temperatures EN1092-1, PN40: DN50, DN80, DN100, and DN150 ① Atmospheric Allowable operating pressures Allowable operating temperatures SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 249 Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves ASME B16.5, Class 150: 2", 3", and 4" NPS ① Atmospheric Allowable operating pressures Allowable operating temperatures ASME B16.5, Class 300: 2", 3", and 4" NPS ① Atmospheric Allowable operating pressures Allowable operating temperatures SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 250: Ptfe Flanged Encapsulated Antenna

    Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves A.5.4 PTFE flanged encapsulated antenna ASME B16.5, Class 150: 2", 3", 4", and 6" NPS ① Atmospheric Allowable operating pressures Allowable operating temperatures JIS B 2220, 10K: 50A, 80A, 100A, and 150A ①...
  • Page 251: Aluminum Horn, With Polypropylene Lens Antenna Version With Polypropylene Flange 3 Inch/80 Mm Size Only

    Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves EN1092-1, PN10/16: DN50, DN80, DN100, and DN150 ① Atmospheric Allowable operating pressures Allowable operating temperatures A.5.5 Aluminum horn, with polypropylene lens antenna version with polypropylene flange 3 inch/80 mm size only ①...
  • Page 252: Pvdf Antenna

    Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves A.5.6 PVDF antenna ASME B1.20.1 2" NPT, EN ISO 228-1 2" G (BSPP), EN 10226-1 2" R (BSPT) ① Atmospheric Allowable operating pressures Allowable operating temperatures A.5.7 Hygienic encapsulated antenna DIN 11851 Sanitary/Hygienic nozzle/slotted nut: DN50, DN80, and DN100 DIN 11864-1 Aseptic/Hygienic nozzle/slotted nut: DN50, DN80, and DN100 SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 253 Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves ① Atmospheric Allowable operating pressures Allowable operating temperatures SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 254 Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves DIN 11864-2 Aseptic/Hygienic flanged: DN50, DN80, and DN100 ① Atmospheric Allowable operating pressures Allowable operating temperatures Note For pressure applications, all attachment hardware must be suitably rated. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 255 Appendix A: Technical reference A.5 Process Pressure/Temperature derating curves DIN 11864-3 Aseptic/Hygienic clamp: DN50, DN80, and DN100 IS0 2852 Sanitary/Hygienic clamp: 2", 3", and 4" Tuchenhagen Varivent face seal clamp: Type N (68 mm) and Type F (50 mm) ① Atmospheric Allowable operating pressures Allowable operating temperatures...
  • Page 256: Loop Power

    ③ Loop resistance RL ④ Loop current IL ⑤ LR250 A.6.1 Allowable operating area of SITRANS LR250 Note The curves below apply to a standalone device, configured via the Siemens handheld programmer. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 257: Curve 1 (General Purpose, Intrinsically Safe, Non-Sparking, Non-Incendive)

    Appendix A: Technical reference A.6 Loop power A.6.2 Curve 1 (General Purpose, Intrinsically Safe, Non-Sparking, Non-incendive) Loop Voltage versus Loop Resistance Note When using HART communications, the minimum voltage with 220 Ohms (RL) is 16.3 V DC. A.6.3 Curve 2 (Flameproof, Increased Safety, Explosion-proof) Loop Voltage versus Loop Resistance Note When using HART communications, the minimum voltage with 220 Ohms (RL) is 20.94 V...
  • Page 258: Startup Behavior

    Appendix A: Technical reference A.7 Startup behavior Startup behavior ● The device draws less than 3.6 mA at startup. ● Time to first measurement is less than 50 seconds. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 259: Appendix B: Hart Communications

    The radar device can be configured over the HART network using either the HART Communicator 375 by Fisher-Rosemount, or a software package. The recommended software package is the SIMATIC Process Device Manager (PDM) by Siemens. SIMATIC PDM This software package is designed to permit easy configuration, monitoring, and troubleshooting of HART devices.
  • Page 260: Hart Communicator 375 Menu Structure

    Appendix B: HART communications B.4 HART Communicator 375 menu structure HART Communicator 375 menu structure Note HART Communicator 375 is supported by SITRANS LR250 HART. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 261 Appendix B: HART communications B.4 HART Communicator 375 menu structure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 262: Hart Version

    Appendix B: HART communications B.5 HART version HART version SITRANS LR250 conforms to HART rev. 5. B.5.1 Burst Mode SITRANS LR250 does not support burst mode. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 263: Appendix C: Certificates And Support

    In addition to our documentation, Siemens provides a comprehensive support solution at: ● Services & Support (http://www.siemens.com/automation/service&support) Personal contact If you have additional questions about the device, please contact your Siemens personal contact at: ● Partner (http://www.automation.siemens.com/partner) To find the personal contact for your product, go to "All Products and Branches" and select "Products &...
  • Page 264 Appendix C: Certificates and support C.2 Certificates SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 265: List Of Abbreviations

    List of abbreviations Short form Long form Description Units 3-A Sanitary Standards, Inc. CE / FM / CSA Conformité Européene / Factory Mutual safety approval / Canadian Standards Association Internal capacitance Dialog to analog Distributed Control System control room apparatus dielectric constant Electronic Device Description EHEDG...
  • Page 266 List of abbreviations SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 267: Lcd Menu Structure

    LCD menu structure 14.1 LCD menu structure Note • In Navigation mode, ARROW keys ( ) navigate the menu in the direction of the arrow. See Parameter Reference (Page 113) for detailed information and instructions. SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 268 LCD menu structure 14.1 LCD menu structure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 269 LCD menu structure 14.1 LCD menu structure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 270 LCD menu structure 14.1 LCD menu structure SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...
  • Page 271: Glossary

    Glossary accuracy degree of conformity of a measure to a standard or a true value. algorithm a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps. ambient temperature the temperature of the surrounding air that comes in contact with the enclosure of the device. antenna an aerial which sends out and receives a signal in a specific direction.
  • Page 272 Glossary blanking a blind zone extending away from the reference point plus any additional shield length.The device is programmed to ignore this zone. capacitance the property of a system of conductors and dielectrics that permits the storage of electricity when potential differences exist between the conductors. Its value is expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a Farad.
  • Page 273 Glossary Echo Confidence describes the quality of an echo. Higher values represent higher quality. Echo Threshold defines the minimum value required for an echo to be accepted as valid and evaluated. Echo Lock Window a window centered on an echo in order to locate and display the echo’s position and true reading.
  • Page 274 Glossary horn antenna a conical, horn-shaped antenna which focuses microwave signals. The larger the horn diameter, the more focused the radar beam. inductance the property of an electric circuit by virtue of which a varying current induces an electromotive force in that circuit or in a neighboring circuit. The unit is a Henry. microwaves the term for the electromagnetic frequencies occupying the portion of the radio frequency spectrum from 1 GHz to 300 GHz.
  • Page 275 Glossary pulse radar a radar type that directly measures distance using short microwave pulses. Distance is determined by the return transit time. radar radar is an acronym for RAdio Detection And Ranging. A device that radiates electromagnetic waves and utilizes the reflection of such waves from distant objects to determine their existence or position.
  • Page 276 Glossary stilling-well see stillpipe. stillpipe a pipe that is mounted inside a vessel parallel to the vessel wall, and is open to the vessel at the bottom. TVT (Time Varying Threshold) a time-varying curve that determines the threshold level above which echoes are determined to be valid.
  • Page 277: Index

    Index bypass pipe see stillpipe, 32 " technical data"; process connection", cables requirements, 40 Calibration Interval, 150 Abbreviations and identifications list, 265 calibration schedules via PDM, 83 access control Certificates, 263 remote access, 155 cleaning activating, 50 instructions, 161 agitator blade detection CLEF (Constrained Leading Edge Fit) avoiding, 130 explanation, 236...
  • Page 278 Index flat face flange, 227 false echo raised face flange, 222, 222, 225 see Auto False Echo Suppression, 238 threaded horn with extension, 190, 193 Far Range threaded PVDF antenna, 220 explanation, 240 Disassembly, 38 setup, 127 flange Disposal, 165 Documentation, 263 bolting instructions, 36 flange markings...
  • Page 279 Index Modifications correct usage, 17 Language, 156 improper, 17 LCD display mounting contrast adjustment, 153 bypass requirements, 32 echo profile viewing, 62 handheld programmer access, 31 fast mode, 153 housing construction, 26, 32 measurement mode, 51 nozzle design, 29 lens nozzle location, 30 replacement, 163 on vessel with obstructions, 32...
  • Page 280 Index programmer threaded horn, 190, 193 handheld, 53 threaded PVDF horn, 220 programming Service, 263 adjust parameters via PDM, 76 Service & Support, 263 via the handheld programmer, 54 Internet, 263 service schedules via PDM, 83 propogation factor values, 128 settings adjust parameters via PDM, 76 sidepipe...
  • Page 281 Index troubleshooting communication, 167 operation, 172 TVT (time varying threshold) explanation, 234 TVT Shaper manual adjustment via PDM, 80 via PDM, 78 unlock value local access, 155 vessel shape selection, 123 Warranty, 12 Wear powered hours, 86 poweron resets, 86 view via PDM, 86 wiring cables, 40...
  • Page 282 Index SITRANS LR250 with mA/HART Operating Instructions, 10/2019, A5E32220602-AG...

This manual is also suitable for:

Sitrans lr2507ml54327ml5433

Table of Contents