Commissioning
6.3 Application examples
Propagation Factor/Stillpipe Diameter
A
Values
Nominal Pipe Size
Propagation Factor
CLEF Range (2.8.4.4.) settings Low calibra-
Since pipe dimensions may vary slightly, the propagation factor may also vary.
a)
CLEF range covers the whole measurement range except first 700 or 1000 mm from sensor refer-
b)
ence point
Note
Flanged and Hygienic encapsulated antenna
For Flanged encapsulated antenna (7ML5432) and Hygienic encapsulated antenna
(7ML5433 ) match the process connection size to the pipe diameter. For example, DN80/3"
flange to DN80/3" pipe.
68
sensor reference point
air gap
700 or 1000 mm (see CLEF Range settings in table below)
a)
low calibration point
CLEF range 2.8.4.4.
Range
0.3 to 1.0 depending on pipe size
Default
1.0000
40 mm (1.5")
50 mm (2")
0.9844
0.988
Low calibra-
tion point -
tion point -
700 mm
700 mm
(2.29 ft)
(2.29 ft)
b)
b)
Operating Instructions, 10/2019, A5E32220602-AG
80 mm (3")
100 mm (4")
0.9935
0.9965
Low calibration
Low calibration
point -1000 mm
point -1000 mm
(3.28 ft)
(3.28 ft)
b)
SITRANS LR250 with mA/HART
b)