Siemens 7ML5431 Operating Instructions Manual page 127

Radar transmitters with ma/hart
Table of Contents

Advertisement

Signal Processing (2.8.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
Near Range (2.8.1.)
The range in front of the device (measured from the sensor reference point) within which any
echoes will be ignored. This is sometimes referred to as blanking or a dead zone. The
factory setting is 50 mm (2") past the end of the antenna, and the default is dependent on the
antenna type and process connection. [See Dimension drawings (Page 183) for antenna
heights.]
Values
Related parameters
Far Range (2.8.2.)
Note
Far Range can extend beyond the bottom of the vessel.
Allows the material level to drop below Low Calibration Point without generating a Loss of
Echo (LOE) state. See Sensor Mode (2.2.2.) for an illustration.
Values
Related parameters
Use this feature if the measured surface can drop below the Low Cal. Point in normal
operation.
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
Range: 0 to 20 m (0 to 65.6 ft)
Default depends on antenna type and process connection:
Units (2.2.1.)
Range: Min. = Low Calibration Pt.
Max. = 23 m (75.45 ft)
Default: Value for Low Calibration Pt. + 1 m (3.28 ft)
Units (2.2.1.)
Parameter reference
127