Self Test; Loop Test; Configuration Flag Reset; Master Reset - Siemens 7ML5431 Operating Instructions Manual

Radar transmitters with ma/hart
Table of Contents

Advertisement

If a volume application is selected, mA Output is automatically set to Volume. See Analog
Output (Page 241) for more details.
1. Open the menu Device – Select Analog Output.
2. Select Analog Output window displays the current setting: click OK.
3. Select a different setting and click OK.
4. Select Analog Output window displays the new setting: click OK.
7.1.6.9

Self test

Checks memory (RAM and Flash). If there are no errors, returns the message 'Self Test OK.'
If errors are found, returns the message 'Self Test Fails'.
Open the menu Device – Self Test, select Yes and click OK.
7.1.6.10

Loop test

Note
The simulated AO (Analog Output) value influences output to the control system.
Allows you to input a simulated value (4 mA, 20 mA, or a user-defined value) in order to test
the functioning of the mA connections during commissioning or maintenance of the device.
The range is 3.56 mA to 22.6 mA, see mA Output Value (2.6.6.).
To simulate a user-defined mA value:
1. Open the menu Device – Loop Test.
2. Select Other, enter the new value, and click on OK. The message 'Field Device fixed at
[new value]' appears. Click on OK. The Loop Test window remains open.
3. When you are ready to end simulation, select End and click on OK to return the device to
the actual output value.
7.1.6.11

Configuration flag reset

To reset the configuration flag to zero, open the menu Device – Configuration Flag Reset
and perform a reset.
7.1.6.12

Master reset

SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
Remote operation
7.1 Operating via SIMATIC PDM
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr2507ml54327ml5433

Table of Contents