Connecting

5.3 Wiring setups for hazardous area installations

Connecting HART
Typical PLC/mA configuration with HART
Note
• Depending on the system design, the power supply may be separate from the PLC, or
integral to it.
• HART resistance (total loop resistance, that is, cable resistance plus 250 Ohm [resistor])
must be limited according to the allowable operating area as shown in either Curve 1
(Page 257) (General Purpose, Intrinsically Safe, Non-Sparking, Non-incendive) or Curve
2 (Page 257) (Flameproof, Increased Safety, Explosion-proof).
5.3
Wiring setups for hazardous area installations
There are six wiring options for hazardous area installations:
● Intrinsically Safe wiring (Page 43)
● Non-Sparking wiring (Page 44)
● Non-incendive wiring (US/Canada only) (Page 45)
● Flameproof wiring (Page 45)
● Increased safety wiring (Page 46)
● Explosion-proof wiring (US/Canada only) (Page 46)
In all cases, check the nameplate on your instrument, confirm the approval rating, and
perform installation and wiring according to your local safety codes.
42
Power supply
SITRANS LR250
R = 250 Ω
Active PLC
HART modem
HART communicator
Operating Instructions, 10/2019, A5E32220602-AG
SITRANS LR250 with mA/HART