PGV...-F200/-F200A...-R4-V19
Commissioning
4.3.2

External Parameterization Using Code Cards

During external parameterization, the reader scans special code cards optically and configures
the relevant parameters. Simply hold the corresponding code cards at the correct distance in
front of the lens on the reader. The standard code cards are in the appendix.
The following parameters can be configured using code cards:
Reader resolution [0.1 mm, 1 mm, 10 mm]
Reader orientation [0°; 180°; 0° or 180°, 0°, 90°, 180° or 270°]
Trigger source [auto, hardware]
Function of input 1 [none, trigger input]
Function of output 1 [none, speed exceeded, warning, fault, contamination, event, no
position]
Function of output 2 [none, speed exceeded, warning, fault, contamination, event, no
position]
Function of output 3 [none, speed exceeded, warning, fault, contamination, event, no
position]
Activating Programming Mode
Note
External parameterization of the reader using code cards must be started within 10 minutes of
the reader switching on. A time lock disables the reader once this time has elapsed. The time
lock remains inactive during the parameterization process. The time lock disables the reader
only if no parameterization activities take place for more than 10 minutes.
If a button is pressed when the time lock is enabled, all LEDs flash and remain lit for 2 seconds
during each flashing cycle.
The changeover from normal operation to parameterization mode is made by pressing button 2
on the back of the reader.
Activating Parameterization Mode
1.
Press button 2 for longer than 2 seconds.
Yellow LED3 now flashes.
2.
Hold the "ENABLE" code in front of the camera system on the reader to trigger final activation
If the "ENABLE" activation code is detected, the green LED2 lights up for 1 second. If the
activation code is not detected, LED2 lights up red for 2 seconds.
Completing Parameterization
1.
Place the parameterization code in the field of vision of the camera module.
After the parameterization code is detected, the green LED2 lights up for 1 second. In the
event of an invalid parameterization code, LED2 lights up red for 2 seconds.
Exiting Parameterization Mode
1.
Hold the "STORE" code in front of the camera system on the reader to save the configuration
If the "STORE" memory code is detected, the green LED2 lights up for 1 second. The
parameterization is stored in the nonvolatile memory of the reader and parameterization
mode is terminated. Parameterization of the reader is now complete. If the memory code is
not detected, LED2 lights up red for 2 seconds.