3. Terminal arrangement diagram
C1
A
RS-485
B
FG
Terminal blocks of controller:
1 is common terminal COM1; 2 is input terminal for emergent stop signal; 3 is remotely controlled
on/off signal input terminal; 4 terminal is used to detect oil filter blocked; 6 is RS485 A; 7 is RS485 B;
8 is the simulated ground (Earth);17 and 18 are the AC20V power source;22、23 terminals are
Pressure Sensor signal input;24、25、26 terminals are motor mutual inductor CT1 input;27、28、2
terminals are Fan mutual inductor CT2 input;30、31 terminals are Temperature Sensor signal input;
19、 20、 21 terminals Used to detect the phase sequence and voltage; 13 terminals is common terminal
of output relay;14 terminals controls fan;15 terminals controls load valve;16 terminals controls
angle-shaped contactor;17 terminals controls star-shaped contactor;18 terminals controls main
contactor.
NOTE: Eelectromagnetism coil shall be connected with surge absorber during
wiring, and dotted lines are extendable functions.
5. Control principles
1. Local Automatic control
①. Press down start button for starting: (Y-△start)
There is fives of self-test after controller is energized and it can not be started by pressing start
、
21
19
11
12
20
uc
ub ua
Figure 4.2.1 Terminal arrangement diagram
△
13 14 15 16 17 18
a
b
CT2
c
A
CT1
B
C