5. User Parameter (Customer Parameter):
In primary menu,
press the move button to move the black slider to the "USER PARA."
menu, press the shift button to switch to the following menu:
LOAD PRES:
00.65MPa
In this menu, Press shift button ,Switch to the following interface requirements to enter
a user password
PASSWORD:0***
After showing this interface, The first bit data or password started flashing, press
"increase button" or "descending button" to modify the flashing data equal to
the first bit of password,Press the shift button, move the cursor to the next data
bit, modify the current data is equal to the second password data, Accordance
with the above, modify the third and fourth Finally, press the "Set button" to
confirm the input, the system verify t
interface:
LOAD PRES:
00.65MPa
In as shown above interface, press "enter button", then the data of loading pressure start to
flash, users can press "increase button" or "Descending button" to modify the present data.
When finished, press "
short voice to tip.
6. Customer Parameter and Functions
Parameters
LOAD PRES.
UNLOAD PRES.
FAN START TEMP
FAN STOP TEMP
MOTOR DELAY T
FAN DELAY T
STAR DELAY TIME
LOAD DELAY TIME
EMPTY DELAY T
The upper right corner with "* "prompt said
*
the system has passed the password authentication
Set Button
" to confirm and save. the controller prompt sends out the
Preset Value
Functions
*.**MPa
LOADING PRESSURE VALUE
*.**Mpa
UNLOADING PRESSURE VALUE
Control the fan starting. This value will be set as
***℃
"120℃" if there is no fan present or the fan is not
required to be protected."
***℃
Control the stopping of the fan
When using the controller to protect the motor, it is
required that the time set here will not meet the
0008S
impulse starting current of the motor, the value
here must be longer than the STAR DELAY TIME
plus LOAD DELAY TIME
When using the controller to protect the motor, it is
0006S
required that the time set here will not meet the
impulse starting current of the motor.
0006S
Star pressure descending start delay time.
The loading delay time after star pressure
0002S
descending.
Load free continuous running time, the machine will
0020M
automatically stop after this time
he password is correct, switch to the following

Advertisement

loading