STOP DELAY TIME
START DELAY T
START MODE
LOAD MODE
COM MODE
COM ADDRESS
SEQ STATE
TOGGLES TIME
SEQ NUMER
SEQ LOAD PRES.
SEQ U.L. PRES.
SEQ DELAY
OIL FILTER
O/A FILTER
AIR FILTER
LUBE
GREASE
BELT
OIL FILTER
The machine will not stop until the load free running
0010S
status lasting till this time
Machine can not be restarted before this set time
0100S
after stopped or over time operation at load free
state
When the remote mode is set, both the button on
the controller and the remote control button can
LOCAL/FAR
turn on and off the machines; When the near mode
is set, only the button on the controller can turn on
and off the machines.
When the manual mode is set, the Load/Unload
AUTO/MAN
function can only be executed by pressing
U
"load/unload 'button
When this is set as "BAN" the communication
function is not available
BAN/COMP.
When this is set as "COMP. "the Controller as a
/BLOCK
slave, in accordance with MODBUS protocol
communications with external devices
When this is set block, block control active
0255
Communication address
Service as main or assistant air compressor during
SLAVE
interlocking operation. The MAIN controls the
SLAVE
During interlocking operation, if one air compressor
continuously operates for time period more than
time set here and rest time of one air compressor in
9999 Hours
interlocking network has reached the time set here,
alternative rest is achieved by starting the resting
air compressor and stopping the operating air
compressor
Number of air compressors in interlocking network
0016
during interlocking operation
The main air compressor searches for one device in
the interlocking network for loading or starting
*.**MPa
when main air compressor's gas supply pressure is
less than the value set here during interlocking
operation
The main air compressor searches for one device in
the interlocking network for unloading or stopping
when main air compressor's gas supply pressure is
*.**MPa
more than the value set here during interlocking
operation
The least waiting time that the main air compressor
0030S
needs to continuously sends control commands
two time
0000H
Reset time for the duration of oil filter changing
0000H
Reset time for O/G Separator changing
0000H
Reset time for gas filter changing
0000H
Reset time for Lubricate Oil Changing
0000H
Reset time for Lubricate Grease Changing
0000H
Reset time for Belt Grease Changing
9999H
Set this value to "0" will make the oil filter alarm not
available