BEAM INTERRUPTION ADJUSTMENT

Initial setting is at 50 ms for
normal work.
According to the speed of a
supposed target you select one
specific setting out of 4 steps.
Set the beam interruption
adjustment switches of the
Receiver according to the speed
of the human object to detect.
4-5

ADJUSTING OUTPUT

-Setting the battery saving timer
Even if the following events are occurred frequently,
each outputs are generated with the intervals as below
to save the battery drain.
Receiver Transmitter
OFF
ON
• Alarm output:
1 output/2 minute
• D.Q. output:
1 output/2 minute
• Low battery output: 1 output/15 minutes
Remove all batteries prior to replacing with new ones.
If this is not followed, the low battery indicator
LED will not reset and continue to flicker.
5

OPERATION CHECK

5-1

LED INDICATION

Receiver
Alarm indicator LED
Low battery LED
5-2
OPERATION CHECK
After installation is complete, be sure to check the operation.
See "Setting the battery saving timer" in "4-5" to turn OFF the battery saving mode.
1
Make sure that the alarm indicator is off.
2
If it is illuminated even when the beams are
not blocked, make optical alignment again.
Check that the low battery indicators on both
3
transmitter and receiver are OFF.
If the LED is flickering, the battery power is low.
Replace with the new batteries.
SELECTOR
POSITION
Typical
interruption
time setting
Caution
Transmitter
Power LED
Low battery LED
Running
Jogging
(50 msec)
(100 msec)
-Setting the intermittent output function
When wireless configuration is being used, which is
unable to determine whether the alarm output
continues, setting the intermittent output function to the
"ON" position, turns on the intermittent alarm output.
This configures the wireless transmitter to send alarms
at a specific time intervals.
Receiver Transmitter
OFF
ON
Intermittent Output Times
• Alarm output:
• D.Q. output:
• Low battery output: 1 output/5 minutes
DETECTOR STATUS
Power ON
Detection (beam interruption)
Low battery power
Receiver
Low battery LED
- 14 -
Walking
Slow movement
(250 msec)
(500 msec)
1 output/1 minute
1 output/1 minute
LED Indications
The power LED turns ON.
The alarm LED turns ON.
The low battery LED flickers.
Alarm indicator LED