No.59-3224-1 2309-26 INSTALLATION INSTRUCTIONS Indoor Recessed Mount PIR Detector Indoor Recessed Mount PIR Detector AP-20NBR(C) AP-20NBR(C) Curtain area/Battery operated model 6.0 m (20') curtain detection area at 4.5 m (14'9") mounting height << Contents >> Before installation Page - Manufacturer's statement - Parts identification Settings Installation...
Before installation - Manufacturer's statement Symbol Meaning Symbol Meaning Check mark indicates recommendation. Failure to follow the instructions provided with this indication Warning Nix sign indicates prohibition. and improper handling may cause death or serious injury. Failure to follow the instructions provided with this indication Special attention is required to the Caution NOTE...
- Parts identifications Base cover Alarm output mode PIR sensitivity Battery saving timer Tamper switch Top cover Lens Accessories Mounting Bezel for an 86-type box Retaining spring x 2 Fixing screw Screw cap x 2...
Settings Disassemble Open the base cover for setting of the detector. Jumper pin settings Alarm output mode PIR sensitivity Turn the jumper PIN by 90 degrees to prevent interference with the casing. N.C. (default) N.O. (recommended) (default) Mounting height: > 3.5 m 3.0 to 3.5 m <...
Installation 2-1. Ceiling/Wall mount without switch box Accessories Install a retaining spring on both sides. used in this installation (follow the illustrated arrow steps to complete the assembly of the retaining spring.) Retaining spring x 2 Make a ø45 mm (1.77") hole in the ceiling for mounting. ø45 mm (1.77") Insert the detector into the hole so that the retaining springs come first.
2-2. Ceiling/Wall mount with 86-type box For the 86-type box mount, dual 86-type boxes are recommended NOTE with the additional one used to accommodate the transmitter. Accessories used in this installation Transmitter Mounting Bezel for an 86-type box Alarm Tamper Prepare an 86-type box on the ceiling or back of the wall.
2-3. Wiring [1] Red Power supply: Positive [2] Black Power supply: Negative [3] White Alarm output [4] Yellow Alarm output [5] Green Tamper output [6] Blue Tamper output Case 1: How to connect to battery terminals using the metal plates. Metal plate Metal plate Case 2: When connecting to wired terminals, remove the metal plates.
Checking 3-1. Walk test Power on. Wait for 60 seconds to complete the warm-up time. 60 s Power Walk in the detection area to check the detecting performance. Start operation.
Others - Specifications Model AP-20NBR(C) Detection method Passive infrared < Ceiling mount > < Wall mount > 6.0 m x 1.0 m (20' x 3'3") 6.0 m x 4.5 m (20' x 14'9") Detection area at 4.5 m (14'9") height at 1.5 m (4'11") height 2.5 m to 4.5 m 1.5 m (4'11"): Horizontal...
- Dimensions With 86-type box mount Without switch box mount 102 (4.02) 86 (3.39) Unit: mm (inch) - Detection area Ceiling mount Maximum detection area Mounting height (H) (8'2") (9'11") (11'6") (13'1") (14'9") Area depth (W) (2') (2'4") (2'7") (2'11") (3'3") Area width (L) (10'10")
- Timing chart Walk test mode Low power mode 10 minutes after power on < 120 s/5 s > 120 s/5 s Detection PIR detection signal Stand-by Pulse count 2 No alarm signal output Alarm output Alarm output Stand-by LED off LED off LED on LED output...