2. Quick start guide
2.4 Starting the device
The configured device must now be started by the master:
In order to send PDO-messages the sensor has to be set to OPERATIONAL mode
■
Master transmits:
EN
ID
00h
(0 = all nodes)
The sensor is now in OPERATIONAL mode
Depending on the previous selected transmission type the master needs to send the
■
SYNC object:
Master transmits:
ID
80h
The received data now looks like (depending on configuration):
ID
180h +
Node-ID
This data is called TPDO.
2.5 Service Data Object (SDO)
2.5.1 SDO read object
The SDO read object to read an dictionary entry:
Master transmits:
ID
DLC Byte0 Byte1 Byte2 Byte3
600h +
8
Node-ID
MH-4 CAN replies:
ID
DLC Byte0 Byte1 Byte2 Byte3
580h +
8
Node-ID
8
DLC
Byte0
2
01h
DLC
0
DLC
Byte0
5
CS =
LSB
40h
Index
CS
LSB
Index
Byte1
Node-ID
Byte1
Byte2
6130h subindex 1
Byte4
MSB
Subindex
00h
Byte4
MSB
Subindex
LSB
WIKA special documentation, model MH-4-CAN
Byte3
Byte4
6150h
subindex 1
Byte5
Byte6
Byte7
00h
00h
00h
Byte5
Byte6
Byte7
MSB
Data