Factory Setting; Mpi Subnet - Siemens SIMOTION C 230-2 Operating Instructions Manual

Hide thumbs Also See for SIMOTION C 230-2:
Table of Contents

Advertisement

Connecting
6.2 Networking
Loading the PROFINET configuration via Ethernet (loading of the IP address)
If a PROFIBUS DP is not available for the initial loading of the IP address, the following procedure
starting from Windows 2000 can be used: The "Automatically Assign IP Address" setting must be
enabled in the TCP/IP configuration of the PC.
1. Connecting a Windows PC and C240 PN directly via RJ45 crossover cable
2. Boot the Windows PC. The PC does not find a DHCP server and automatically selects an IP
address from the APIPA subnet (Automatic Private IP Addressing) 169.254.0.0.
3. Load the new hardware configuration with the new IP address via Ethernet to IP address
169.254.11.22 (default IP address of the SIMOTION C as delivered)
Note
You can also write the user project and/or configuration with SIMOTION SCOUT and the menu
command "Load to file system" directly from the PC to the memory card (micro memory card).
To do this, select the device in the project navigator and execute the "Load to file system"
command in the context menu.
6.2.6

Factory setting

After resetting the SIMOTION C to the factory setting (see chapter Setting SIMOTION C to factory
settings (Page 150)) or when the module is delivered, the following addresses are set:
• Baud rate = 1.5 Mbit/s
• PROFIBUS address for the interfaces X8 = 2 and X9 = 2
• Ethernet interface:
IP address = 169.254.11.22
Subnet mask = 255.255.0.0
Router address = do not use a router
• PROFINET interface X11 (C240 PN)
IP address = no valid address
Subnet mask = no valid address
Router: Do not use a router
6.2.7

MPI subnet

An MPI subnet has the same basic configuration as a PROFIBUS subnet. The installation rules,
stated in the chapter Configuring a PROFIBUS subnet (Page 119), therefore apply.
128
Operating Instructions, 11/2022, A5E33441428B
SIMOTION C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion c240Simotion c240 pn

Table of Contents