Siemens SIMOTION C 230-2 Operating Instructions Manual page 101

Hide thumbs Also See for SIMOTION C 230-2:
Table of Contents

Advertisement

Pin assignment
The table below shows the pin connections on the screw-type terminal block.
Table 6-6
Terminal
M
L+
M
If you want to ground the reference potential, you must not remove the jumper between
terminals M and functional ground on the SIMOTION C.
Line buffering
The PS 307 load current supplies from the S7-300 system guarantee mains buffering for 20 ms.
Figure 6-6
Supply system lines
Use flexible cables with a cross-section of 0.25 to 2.5 mm
power supply.
If you only use one wire per connection, a ferrule is not required.
You can use ferrules without an insulating collar in accordance with DIN 46228, Form A long
version.
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
Assignment of the screw-type terminal block
Pin assignment
Functional ground
Ground
24 V DC
Ground
Module supply options
(or AWG 18 to AWG 14) for wiring the
2
Connecting
6.1 Wiring
101