Climatic environmental conditions
The SIMOTION C may be used under the following climatic environmental conditions:
Table 11-18
Environmental conditions
Temperature:
Horizontal mounting:
Vertical mounting
Relative humidity
Atmospheric pressure
Contaminant concentration
Moisture condensation and
ice formation
Mechanical environmental conditions
The mechanical environmental conditions for the SIMOTION C are specified in the following
table in terms of sinusoidal vibrations.
Table 11-19
Mechanical environmen‐
Vibration tested in accord‐
ance with DIN EN
60068-2-68
Shock resistance tested in
accordance with
DIN EN 60068-2-27
Reduction of vibration
If the SIMOTION C is subjected to greater shocks or vibrations, you must take appropriate
measures to reduce the acceleration or the amplitude.
Installation on damping material (e.g. rubber-bonded metals) is recommended.
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
11.4 Mechanical and climatic environmental conditions for operation of the SIMOTION C
Climatic environmental conditions
From 0 to 55° C
From 0 to 40° C
From 5% to 95%
1,060 to 700 hPa
SO
Relative humidity <60%,
no condensation
H
Relative humidity <60%,
no condensation
Not permitted
Mechanical environmental conditions
tal conditions
10 to 58 Hz: 0.35 mm
58 to 200 Hz: 50 m/s
10 g peak value, 6 ms duration
100 shocks in each of the 3 axes ver‐
tical to one another
Range of application
: < 0.5 ppm;
2
S: < 0.1 ppm;
2
Operation
2
Technical data
Comments
-
Without condensation, corre‐
sponds to relative humidity (RH)
severity level 2 in accordance with
IEC 1131-2
Corresponds to an altitude of
mean sea level to 3,000 m
Test:
10 ppm; 4 days
1 ppm; 4 days
Transport (in packaging)
5 to 9 Hz: 3.5 mm
9 to 200 Hz: 10 m/s
2
10 g peak value, 6 ms duration
100 shocks in each of the 3 axes
vertical to one another