2.6.2 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Ring
To premises phones
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
7 foot cable
(MCBL-7)
order separately
Male Plug
Connectors
Female
Connectors
DACT-UD2
Figure 2.14 Wiring Phone Jacks
Incoming Telco Phone
Green Wire
Ring
Red Wire
Tip
To premises phones
Primary Phone Line PRI
CAUTION: It is critical that the
DACT-UD2 be located as the first
device on the incoming telephone
circuit to properly function
Installation
Primary Lines
Lines
Ring
Tip
55