2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. A typical wiring diagram for the FACP is shown below.
50
4XTMF
Figure 2.9 Typical Power-limited Wiring Requirements
Power-limited Wiring Requirements
SLC-2LS
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010