Appendix D
When configured with an addressable FACP such as the MS-9200(E), the FIRE•COMMAND•25/50 may be trig-
gered either by the FACP main NAC output or from addressable control modules. Figure D-1 illustrates CMD1 trig-
gered by an addressable control module. The addressable control module may trigger the FIRE•COMMAND•25/50
via reverse polarity (shown) or relay contact. The FACP monitors the FIRE•COMMAND•25/50 for faults while in
the standby or alarm state by wiring a monitor module to the trouble contacts as shown in Figure D-1. Activation of
the addressable control module is controlled by the FACP. Refer to the MS-9200(E) manual for additional
information.
FIGURE D-1:
Notes:
Auxiliary Power terminals for special application power only. Wiring must remain in the room.
1.
Supervise the wiring between the FIRE•COMMAND•25/50 Auxiliary Power output and the control module
2.
with an EOL relay (A77-716B)
EOL resistor supplied with modules.
3.
Technical Manuals Online! - http://www.tech-man.com
Addressable Module Connections
Addressable Module Connections
Control
Module
firealarmresources.com
Note 2
Note 1
Document #50580
Rev. C
8/12/97
P/N 50580:C
Monitor
Module