Controls And Indicators; Components - Fire-Lite Alarms ES-200XC Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Product Description

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life
LED backlight that remains illuminated. If AC power is lost and the system is not in alarm,
the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display
and LED indicators as listed below. The key panel, which is visible with the cabinet door closed, has 30 keys, including a 16 key alpha-
numeric pad similar to a telephone keypad.
LED Indicators
LED indicators are provided to annunciate the following conditions:
Fire Alarm (red)
CO Alarm (red)
AC Power (green)
Supervisory (yellow)
Trouble (yellow)
Ground fault (yellow)
Battery fault (yellow)
Disabled (yellow)
Maintenance (yellow)
Communication (yellow)
Alarm Silenced (yellow)
F1-F4 Function Keys (yellow)
Function keys:
Acknowledge
Alarm Silence
Drill
Reset (lamp test)
four (4) programmable function keys
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
First Event and scroll keys
Last Event and scroll keys
Clear key
Escape key
Two cursor keys (left and right)
Menu/Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.

1.4 Components

Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface connectors. The
4XTMF option module plugs in and is mounted to the main circuit board.
IPOTS-COM Communicator Card
The pre-installed IP/POTS communicator card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. It also allows remote programming or interrogation of the control panel using the FS-Tools Upload/Down-
load utility and a hard-wired Ethernet IP connection. Any personal computer with Windows
software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file,
walktest data, current status and system voltages. Refer to Section 6 on page 123 for more information.
The IPOTS-COM digital communicator provides the following POTS functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
16
Figure 1.2 Membrane/Display Panel
®
7 or greater, 32 or 64 bit, and FS-Tools
ES-200X Series Manual — P/N LS10131-000FL-E:C 7/25/2018