5
5-18
Force OFF- is set for the Inputs Default at "IO device Access point tab for
successful operation.
b. Hold Last Image: Input values will be holding. NET LED will be Green.
Network adaptor communication with master intact. IO LED will be red
and fault "Loss/addition of device' logged in I/O fault table. Ensure that –
Hold last State- is set for the Inputs Default at "IO device Access point tab
for successful operation.
c. Auto Reset: This option will reset the profinet Adapter module.
d. Disconnect Profinet: Last input values will not hold. NET LED will be
blinking Green. Network adaptor communication with master stops .IO
LED ill be red and fault "Loss/addition of device' logged in I/O fault table.
Note:
Refer to the examples section in the power modules chapter in New Slice IO
manual for more details about the IO node configuration using the different power
modules.
RSTi Network Adapter Manual User Manual -January 2012
GFK-2746