Specification
GFK-2746
1 Introduction
1-3
Chapter
The following table describes the Specifications of STXPBS001.
Table 2: STXPBS001: Interface and General Specifications
Items
Interface Specification
Redundancy
Repeater Control Signal
Freeze mode
Sync mode
Auto baud rate
Fail safe mode
Station type
FMS support
Number of Station
Number of Expansion I/O slots
I/O Data Size
Indicators
Baud Rate
Module Location
Field Power detection
General Specification
Surrounding Air Temperature/
Ambient Temperature
Relative Humidity
Durable-vib./impact
EMC/ESD
Mount Position
Atmosphere
Field Supply Voltage
Field Supply Current
Mount
System Power
Power Dissipation
Current for I/O Module
Chapter Chapter
Chapter
Specification
Not supported
RS-485 Signal
Support
Support
Support
Support
Slave
Not supported
100 Station/Max (Rotary switch #0~99)
Maximum 32 slots
Total: Input 128bytes/Output 128bytes
Maximum Discrete I/O: Input 1024points/Output
1024points
Maximum Analog I/O: Input 64channels/Output
64channels
1 green/red Module Status Indicator
1 green Network Status Indicator
1 green/red IO Module Status indicator
1 green Field Power Status indicator
9.6K~12M (1.2Km~100m) (Auto baud rate Selection)
Starter module - First side of RSTi system
Detect Field Power @ minimum 11Vdc
-20℃—50℃ for UL applications. -20℃ to 60℃ for non UL
applications. Storage -40℃—85℃
5% ~ 90%, without condensation
IEC68-2-6(2G)/10G at non-driving
EN50082/EN50081
First module of RSTi system
No excessive dust , No corrosive gases
Class 2, 24VDC
24VDC (11VDC ~ 28.8VDC)
Maximum 10A
DIN-Rail
Supply voltage: 24Vdc nominal
Supply voltage range: 11~28.8Vdc
Protection: Output current limit (Minimum 1.5A)
Reverse polarity protection
60mA typical @24Vdc
1.5A @5Vdc
1