DPV1 Write service
Command
Hex
00 00
00000000
00000000
00000000
00 10
00010000
00000001
01 00
00000000
00000001
01 10
00010000
00000000
00 04
00000100
00000000
00 14
00010100
00000001
01 04
00000100
00000001
01 14
00010100
00000000
00 08
00001000
00000000
00 18
00011000
00000001
01 08
00001000
00000001
01 18
00011000
00000000
00 01
00000001
00000000
00 11
00010001
00000001
01 01
00000001
GFK-2746
1 Introduction
1-39
Chapter
The Profibus network module also supports DPV1 service. The details are as below:
Slot#=0, Index 1: Write STXPBS001 extension parameter(2Byte)
Slot#0~31, Index 1: Write parameter for an IO module.
Slot#0~31, Index 2: Write memory data to an IO module.
Slot#= 254: Write user data to EEPROM user area
Index=0~127(Offset in EEPROM user area)
Data Ln=Length for data to be written
Data [0] ~Data[n] =User data
List of valid commands for (Slot#=0, Index 1: Write STXPBS001 extension parameter (2
bytes). Note that the length of parameter may vary depending upon the module chosen for
STXPBS* Network adapter with Integrated IO modules and hence the command word.
Reaction to
Bus Fault
Binary
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
00: Profibus
communication
01: Clear Input
data
01: Clear Input
data
01: Clear Input
data
Chapter Chapter
Chapter
DP Clear Action
Word data
Format
00: Bus Stop IO
fault action
00:INTEL
00: Bus Stop IO
fault action
00:INTEL
00: Bus Stop IO
fault action
01:MOTOROLA
00: Bus Stop IO
fault action
01:MOTOROLA
01: Bus Run (
clear Output)
00:INTEL
01: Bus Run (
clear Output)
00:INTEL
01: Bus Run (
clear Output)
01:MOTOROLA
01: Bus Run (
clear Output)
01:MOTOROLA
10: Bus Run (
Hold Output)
00:INTEL
10: Bus Run (
Hold Output)
00:INTEL
10: Bus Run (
Hold Output)
01:MOTOROLA
10: Bus Run (
Hold Output)
01:MOTOROLA
00: Bus Stop IO
fault action
00:INTEL
00: Bus Stop IO
fault action
00:INTEL
00: Bus Stop IO
fault action
01:MOTOROLA
1
Restart on Bus
fault
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset
01: auto reset
00:Power reset