1
Chapter
1-4
Chapter
Isolation
Field Power
Maximum Current Field Power Contact
Weight
Module Size
Certification
Environment Condition
Technical Specification
Network Type
Network Cable
Cable Length
Communication Speed
Maximum Station No.
Station Type
Expansion No.
Maximum Digital I/O
Maximum Analog I/O
I/O Data Size
Baud rate Setting
Station No. Setting
Power Dissipation
RSTi Network Adapter Manual User Manual - January 2012
System power to internal logic: Non-isolation
System power to I/O driver: Isolation
Supply voltage: 24Vdc nominal
Supply voltage range: 11~28.8Vdc
DC 10A Maximum
155g
42mm x 99mm x 70mm
UL/cUL/CE/PROFIBUS (PNO)
See "Environmental Specifications" in Appendix A.
PROFIBUS-DP
PROFIBUS-DP Special Cable
1.2Km ~ 100m
9.6kBaud ~ 12MBaud
99 Station (Include Master Scanner)
PROFIBUS-DP Slave
Maximum 32 Module
Input: 1024point / Output: 1024point
Input: 64Ch/Output: 64Ch
Input: 128Bytes / Output: 128Bytes
Support Auto-baud rate
Rotary S/W #1, #2 (x10, x1)
60mA
GFK-2746