a. Profibus Communication: Last input values will not hold. NET LED will be
blinking Green. Network adaptor communication with master stops. IO
LED ill be red and fault "Loss of device' logged in I/O fault table.
b. Clear Input Data: Input values will be zero. NET LED will be Green.
Network adaptor communication with master intact. IO LED will be red
and fault "Loss of device' logged in I/O fault table.
c. Stay with last Input data: Input values will be holding. NET LED will be
Green. Network adaptor communication with master intact. IO LED will be
red and fault "Loss of device' logged in I/O fault table.
5. Restart on Bus Fault: If Bus error is detected, the network module will power up
depending upon the options selected for this parameter. The options are "Po er
restart" & "Auto restart".
It should be noted that only (1. Watch dog time base) and (4. Reaction to Bus Fault) are
applicable for STXPBS (Network adapter with Integrated IO modules).
Apart from these settings, for Analog output modules, serial modules, digital output
modules etc., select the module at the "modules" tab and choose properties for additional
settings. Refer to individual module description for more details.
Note:
Refer to the examples section in the Power Modules chapter in New Slice IO
manual for more details about the IO node configuration using the different power
modules.