5
LED Indicators
5-4
Module Status LED (MOD)
Color
Status
Power off
Off
H/W Fault
Invalid boot image header
Green
(Flash), ROM Boot loader
Flashing Red (0.5S)
Flashing Red (0.1S)
Flashing Green
(0.1S)
Green On
Normal Operation
Network Status LED (NET)
Color
Status
Power off
No Connection has been
Off
established with IO-
controller.
Flashing Red (0.1s)
Invalid Configuration
Flashing Green
Wait parameters
(0.1s)
Red
Flashing Red (0.5s)
Flashing Green
(0.5s)
Green
RSTi Network Adapter Manual User Manual -January 2012
Table 36: STXPNS001: Module Status LED
Function
No power is supplied to the unit.
The unit has occurred
unrecoverable fault in self-testing.
Invalid RAM Image
OS Fatal error is occurred
OS Handle Unexpected
Exceptions
The unit is operating in normal
condition.
Table 37: STXPNS001: Network Status LED
Function
Device is not on-line or may not be
powered.
Invalid Configuration
PROFINET IO connection has been
established.
PROFINET IO connection is aborted
after a data exchange has taken
place.
PROFINET IO connection is aborted
before a data exchange has taken
place.
PROFINET IO Data Exchange stop
PROFINET IO Data Exchange Run
Firmware fault