Wilo Yonos GIGA2.0-I Installation And Operating Instructions Manual page 184

Table of Contents

Advertisement

Available languages

Available languages

en
12.7.2
Using the analogue input AI2 as
the setpoint input
Analogue input (AI2)
Signal type
Fig. 76: Analogue input menu (AI2)
Signal type (AI2)
Fig. 77: Signal types menu (AI2)
184
The setpoint to which the pump controls is specified according to "Control settings" section.
The adjustment is made in menu "Control setting" [" 160], "Set setpoint source" [" 163].
"Internal setpoint" must be activated.
The "Cable break detection" function is not active.
Fig. 75: Behaviour of analogue input AI1: Sensor value with signal type 0 ... 10 V / 0 ... 20 mA
The setting of the analogue input AI 2 is only available in the menu if the analogue input
AI2 was previously selected in the menu. To do this, select the following in the menu in
succession:
Universal
1.0
1.1
1.1.9
1.1.9 / 2
The signal type is set via the menu
AI2".
Universal
1.0
1.3
1.3.4
1.3.4.1
Possible signal types when selecting the analogue input as the setpoint input:
Setpoint sensor signal types:
0 ... 10 V: Voltage range from 0 ... 10 V for the transmission of setpoints.
2 ... 10 V: Voltage range from 2 ... 10 V for transmission of setpoints.
0 ... 20 mA: Electric current range from 0 ... 20 mA for the transmission of setpoints.
4 ... 20 mA: electric current range of 4 ... 20 mA for transfer of setpoints.
The analogue input AI2 can only be used as an input for an external setpoint sensor.
Signal type 2 ... 10 V / 4 ... 20 mA:
If an external setpoint sensor is set up at analogue input AI2, the signal type must be set. In
this case 2 ... 10 V or 4 ... 20 mA.
The analogue signal runs between 5 V ... 10 V or between 10 mA ... 20 mA. The analogue sig-
nal is interpolated linearly. The applied analogue signal of 5 V or 10 mA represents the set-
point (for instance the speed) at "0 %". The applied analogue signal of 10 V or 20 mA repres-
ents the setpoint of the differential pressure at "100 %". (See diagram Fig. 78).
Installation and operating instructions • Wilo-Yonos GIGA2.0-I/-D • Ed.01/2023-03
Display text
Settings
Control settings
Setpoint source
Analogue input (AI2)
"Settings", "External interfaces", "Analogue input
Display text
Settings
External interfaces
Analogue input (AI2)
Signal type