[Sense:]Frequency:aperture; [Sense:]Function:condition; [Sense:]Frequency:aperture? (@<Channel>); [Sense:]Function:condition (@<Ch_List>) - HP E1419A User Manual

Measurement and control module
Table of Contents

Advertisement

[SENSe:]FREQuency:APERture?

Parameters
Comments

[SENSe:]FUNCtion:CONDition

Parameters
Comments
Usage
Chapter 6
[SENSe:]FREQuency:APERture? <ch_list> returns the frequency counting gate
time.
Parameter
Parameter
Name
Type
channel
string
If the channels specified are on an SCP that doesn't support this function, an error
will be generated. See your SCP's User's Manual for its capabilities.
Related Commands: SENSe:FREQuency:APERture
Returned Value: returns numeric gate time in seconds, The type is float32.
[SENSe:]FUNCtion:CONDition <ch_list> sets the SENSe function to input the
digital state for channels in <ch_list>. Also configures digital SCP channels as
inputs (this is the *RST condition for all digital I/O channels).
Parameter
Parameter
Name
Type
ch_list
string
The HP E1533 SCP senses 8 digital bits on each channel specified by this
command. The HP E1534 SCP senses 1 digital bit on each channel specified by
this command.
If the channels specified are not on a digital SCP, an error will be generated.
Use the INPut:POLarity command to set input logical sense.
Related Commands: INPut:POLarity
*RST Condition: SENS:FUNC:COND and INP:POL NORM for all digital SCP
channels.
To set first four channels of a HP E1534 in SCP position 6, and second 8-bits of
HP E1533 at SCP position 7 to digital inputs send:
SENS:FUNC:COND (@148:151,156)
Range of
Values
132 - 163
Range of
Values
132 - 163
HP E1419 Command Reference 271
[SENSe]
Default
Units
none
Default
Units
none