Wiring The Truvu™ Et Display To The Rnet Port - Carrier VVT Bypass II Installation And Startup Manual

Table of Contents

Advertisement

Wiring the TruVu™ ET Display to the Rnet port
WARNING Do not apply line voltage (main) - 24 Vdc power only.
Wiring power
Wire the TruVu™ ET Display 24V DC connector to the 24 Vdc power supply using 2-conductor 18 AWG wire.
Maximum distance 100 feet (30 meters).
CAUTION The TruVu™ ET Display can share a power supply with the Carrier controller as long as:
The power supply is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.
NOTE Purchase a power supply from a third-party manufacturer.
Wiring communication
1
Turn off the VVT Bypass II's power.
2
Wire the TruVu™ ET Display's RS485 connector to the <ALCProduct>'s Rnet port, Gnd to Gnd, + to Rnet
+, - to Rnet - using 2-conductor 22 AWG wire with a maximum distance of 500 feet (152 meters).
3
Turn on the VVT Bypass II's power.
VVT Bypass II Controller
Installation and Start-up Guide
21
Installing the VVT Bypass II
CARRIER CORPORATION ©2019
All rights reserved