Power extend converter mounting bracket, door, and top cover kits (34 pages)
Summary of Contents for Vertiv NetSure IPE Series
Page 1
NetSure™ IPE Series Rectifier Installation and User Manual (UM1R481000CNA), Revision F Specification Number: 561664, 561665, 561666 Model Number: R48-1000C...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corp., and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corp.
Page 4
Rectifier High Voltage Shutdown and Lockout Restart ..........40 Troubleshooting and Repair ................41 Contact Information ............................41 Troubleshooting ..............................41 Repair ....................................41 DC Power, Outdoor Enclosure & Service Contacts ........43 Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Even a momentary short circuit can cause sparking, explosion, and injury. DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection devices remain de-energized during installation at loads, as required. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
GMT Fuses Ampere Rating Part Number Fuse Color 248610200 Violet 248610300 248610500 Brown 1-1/3 248610700 White 248610800 Orange 248610900 Blue 248611000 Green 7-1/2 248611300 Black-White 248611200 Red-White Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Power Derating Based on Input Voltage: The rectifier power varies with changes in input voltage. It uses an advanced power limitation method. The lower input threshold is 85 VAC. The rectifier can Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 13
At an ambient temperature of +75 °C (+167 °F), the power delivered by the rectifier is 0 W. NOTE! If used outdoors under full solar radiation, in an ambient of 46 °C the product is rated for 561 W per Telcordia GR-487-CORE. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
220 VAC input voltage, and for any duration of AC input interrupts. Under the above conditions, standard AC distribution circuit breakers will not trip. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 15
Input Current Input Voltage Voltage (Amperes) 208/240 Note: At 100% of full load with output adjusted to 58 volts DC as measured at the output terminals. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 16
Input Current Input Voltage Voltage (Amperes) 208/240 Note: At 100% of full load with output adjusted to 58 volts DC as measured at the output terminals. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
The rectifier conforms to the requirements of FCC rules Part 15, Class B for radiated and conducted emissions limits. The rectifier conforms to the requirements of European Norm, EN55022, Class B for radiated and conducted emissions limits. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
, waiting until the LEDs on the rectifier extinguish, then turning power to the rectifier on). If the rectifier does not experience a high voltage condition before the HVSD restart timer expires, the restart circuit is reset. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Inches: 14.2 (Height) X 7.1 (Width) X 3.5 (Depth) Weight: 5 kg (11.0 lbs) Indicators (located behind door): Power (Green LED) Protection (Yellow LED) Alarm (Red LED) Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 21
3. Weight: Rear View Net: 5 kg (11 lbs.) Shipping: 4.61 3.66 7.68 Top View 17.05 14.17 Left Side View Front View Right Side View Bottom View Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
• Crimping Tool with Dies for 6 AWG to 14 AWG • Electrician’s Insulated Screwdrivers, Phillips, No. 1 and 2 • Electrician’s Insulated Screwdrivers, Flat Blade, Small and Large • NO-OX-ID or Approved Equivalent Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Installing the Mounting Bracket to the Pole with the Pole Mount Band Pole Pole Mount Band P/N: 63126330 Torque to 5.08 Nm (45 in-lbs). Mounting Bracket (Big) P/N: 632404V1 Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 24
(2 places) P/N: 26011153 Torque to 13 to 16 Nm (115 to 141 in-lbs). Door hardware (4X) torque is 29 Kgf cm (2.9 Nm) (25 in-lbs). Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Secure the rectifier to the wall using the wall anchors previously installed. Refer to Figure 14. Figure 12: Wall Mounting Hole Positions (0.2) Dia. (16) (inch) Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 26
Mounting Bracket (Big) P/N: 632404V1 Figure 14: Securing the Rectifier to the Wall Wall Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Captive fasteners (for M8 bolts) for frame ground lugs are located on each mounting bracket. Holes are spaced on 1-inch centers. Refer to Figure 16 for location. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Contacts close between terminals 3 and 4 on the alarm connector during an AC fail alarm condition. Terminal 5 on the Alarm Connector: CAN_H. Terminal 6 on the Alarm Connector: CAN_L. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Figure 22 through Figure 24. See also “Customer Wiring to the Mating Connectors” starting on page • Wire size is determined by site requirements. Maximum -48 VDC input wire size is 10 AWG. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
If any of the five (5) connectors located on the bottom of the unit are left unused, screw the provided connector dust cover onto the unused connector. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 31
8. Slide the sealing cable adapter housing into the sleeve. 9. Tighten the rear pressing nut to the sleeve. Torque to 6.5 N m (58 in-lbs). Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 32
8. Slide the sealing cable adapter housing into the sleeve. 9. Tighten the rear pressing nut to the sleeve. Torque to 6.5 N m (58 in-lbs). Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 33
8. Slide the sealing cable adapter housing into the sleeve. 9. Tighten the rear pressing nut to the sleeve. Torque to 6.5 N m (58 in-lbs). Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 34
Load 6: Return to terminal 4+, -48 VDC to terminal 4-. Pins for wire connections. Accepts wires in the range of 22 AWG to 16 AWG. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 35
8. Slide the sealing cable adapter housing into the sleeve. 9. Tighten the rear pressing nut to the sleeve. Torque to 6.5 N m (58 in-lbs). Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 36
Figure 22: Electrical Connections Diagram - External, P/N 561664 (R48-1000C-4) Customer Wiring Connectors Information Designation Vertiv P/N Mfgr P/N AC Input 14190607 CT93-3TK1X DC INPUT Alarm 14190611 CT93-8TK1Y ALARM No Connection No Connection No Connection DC Input 14190615 CT93-8TK1W A001...
Page 37
Figure 23: Electrical Connections Diagram - External, P/N 561665 (R48-1000C-5) Customer Wiring Connectors Information Designation Vertiv P/N Mfgr P/N AC Input 14190607 CT93-3TK1X DC INPUT Alarm 14190611 CT93-8TK1Y ALARM No Connection No Connection No Connection DC Input 14190615 CT93-8TK1W A001...
Page 38
Figure 24: Electrical Connections Diagram - External, P/N 561666 (R48-1000C-6) Customer Wiring Connectors Information Designation Vertiv P/N Mfgr P/N AC Input 14190607 CT93-3TK1X Alarm 14190611 CT93-8TK1Y ALARM DC INPUT DC Output 1 14190609 CT93-8TK1Z DC Input 14190615 CT93-8TK1W A001 DC OUTPUT 2...
Ensure the front door is securely closed and the screws are torqued to 29 Kgf cm (2.9 Nm) (25 in-lbs). Table 8: Status and Alarm Indicators Indicator Normal State Power (Green) Protection (Yellow) Alarm (Red) Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Remove AC input power to the rectifier. Wait 30 seconds or more (until the LEDs on the rectifier extinguish). Re-apply AC input power to the rectifier. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
When a trouble symptom is localized to a faulty rectifier, the rectifier should be replaced in its entirety. No attempt should be made to troubleshoot or repair individual components inside the rectifier enclosure. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
Page 42
If rectifier fails to start or shuts down again; (Red) On for any reason, including replace the rectifier. overvoltage shutdown and internal output fuse open. Vertiv | NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA) | Rev. F...
DC POWER, OUTDOOR ENCLOSURE & SERVICE CONTACTS CUSTOMER SERVICE (PRE-SHIPMENT) Email CustomerService.ESNA@Vertiv.com Call Customer Service for purchase order status, expediting requests and order tracking. Phone 1.800.800.1280 option 1 CUSTOMER SUPPORT CENTER (POST-SHIPMENT) Email ESNACustomerSupportCenter@Vertiv.com After an order has shipped, contact our Customer Support Center with post-shipment related questions, concerns or claims.
Need help?
Do you have a question about the NetSure IPE Series and is the answer not in the manual?
Questions and answers