5.2

Permitted mounting positions

Mounting positions
Only vertical installation with two mounting directions of up to +45° and -45° is permitted for
the device.
With installed Compact Flash card
Rear
0° - 50°C
0° to 45°C
= Installation according to RAL (Restricted Access Location)
1
(installation of device in operating facilities with restricted access, for example, a locked
control cabinet)
The device with DC power supply does not fulfill the requirements according to EN 60950-1
in the power supply unit area. The device must therefore be installed in such a way that it is
part of an operating area with restricted access (e.g. a locked control cabinet, control panel
or server room).
Mechanical environmental conditions
● Vibration
SIMATIC HMI IPC577C
Operating Instructions, 10/2010, A5E02368074-02
Temperature at the device
Front
Max. 40°C
1)
0° to 45°C
WARNING
– Operation, tested in accordance with DIN IEC 60068-2-6
10 to 58 Hz: 0.075 mm 58 to 200 Hz: 0.5 m/s²
– Storage/transport, tested according to IEC 60068-2-27, IEC 60068-2-29
50 m/s2, 30 ms,
250 m/s2, 6 ms,
Installing/Mounting
5.2 Permitted mounting positions
Angle A
+45°
+45°
Angle B
-45°
-45°
37