Parameter Setting Examples - Acsm1; Speed And Torque Control Using The Abb Drives - Enhanced Communication Profile - ABB FENA-01 User Manual

Ethernet adapter module
Hide thumbs Also See for FENA-01:
Table of Contents

Advertisement

72 Modbus/TCP – Start-up
7. Define the process data transferred to and from the drive in
parameter groups 52 and 53.
Note: The adapter module assigns the Control word, Status
word, references 1...2 and actual values 1...2 automatically to
Modbus registers. Process data groups are not available in the
ABB Drives - Classic communication profile.
8. Validate the settings made in parameter groups 51, 52 and 53
with parameter 51.27 FBA PAR REFRESH.
9. Set the relevant drive control parameters to control the drive
according to the application.
Examples of appropriate values are shown in the tables below.
Parameter setting examples – ACSM1
Speed and torque control using the ABB Drives –
Enhanced communication profile
This example shows how to configure a speed and torque control
application that uses the ABB Drives - Enhanced profile. In
addition, some application-specific data is added to the
communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
communication profile
When Reference 1 (REF1) is used, a reference value of ±20000
(4E20h) corresponds to the reference set with parameter 25.02
SPEED SCALING in the forward and reverse directions.
When Reference 2 (REF2) is used, a reference value of ±10000
(2710h) corresponds to the reference set with parameter 32.04
TORQUE REF 1 MAX in the forward and reverse directions.
on page 91.
ABB Drives

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fena-11Fena-21

Table of Contents