Drives - ABB FENA-01 User Manual

Ethernet adapter module
Hide thumbs Also See for FENA-01:
Table of Contents

Advertisement

The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
Output data
Control word
Speed reference
Torque reference
1)
Constant speed
Speed reference for
1)
jogging function 1
1)
Example
The table below gives the recommended drive parameter settings.
Drive parameter
50.01 FBA ENABLE
50.02 COMM LOSS FUNC
50.03 COMM LOSS T OUT
50.04 FBA REF1
MODESEL
50.05 FBA REF2
MODESEL
51.01 FBA TYPE
51.02 FBA PAR2
(PROTOCOL/PROFILE)
51.03 FBA PAR3
(COMMRATE)
51.04 FBA PAR4
(IP CONFIGURATION)
Modbus
Input data
register
(4)00001
Status word
(4)00002
Speed actual value
(4)00003
Torque actual value
(4)00004
Power
(4)00005
(4)00006
DC bus voltage
(4)00007
Setting for ACSM1

drives

Enable
2)
Fault
2)
3.0 s
Speed
Torque
1)
ETHERNET
1 (= MB/TCP ABB E)
2)
0 (= Auto)
2)
0 (= Static IP)
Modbus/TCP – Start-up
Modbus
register
(4)00051
(4)00052
(4)00053
1)
(4)00054
(4)00055
1)
(4)00056
(4)00057
Description
Enables communication
between the drive and the
fieldbus adapter module.
Enables fieldbus communication
fault monitoring.
Defines the fieldbus
communication break
supervision time.
Selects the fieldbus reference 1
scaling.
Selects the fieldbus reference 2
scaling.
Displays the type of the fieldbus
adapter module.
Selects the Modbus/TCP
protocol and the ABB Drives -
Enhanced profile.
Ethernet communication rate is
negotiated automatically by the
device.
Configuration will be obtained
from parameters 05...13.
73