82 Modbus/TCP – Start-up
Parameter setting examples – ACS480 and ACS580
drives
Frequency control using the ABB Drives – Enhanced
communication profile
This example shows how to configure a frequency control
application that uses the ABB Drives - Enhanced profile. In
addition, some application-specific data is added to the
communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
communication profile
In the frequency control mode, when Reference 1 (REF1) is used,
a reference value of ±20000 (4E20h) corresponds to the reference
set with parameter 46.02 Frequency scaling in the forward and
reverse directions.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
Output data
Control word
Frequency reference
Reference 2 (Not used)
Constant frequency 1
Constant frequency 2
1)
Example
The table below gives the recommended drive parameter settings.
Drive parameter
50.01 FBA A enable
50.02 FBA A comm
loss func
on page 91.
Modbus
register
(4)00001
(4)00002
(4)00003
1)
(4)00004
(4)00005
1)
(4)00006
(4)00007
Setting for ACS480
and ACS580 drives
2)
1 = Option slot 1
2)
1 = Fault
ABB Drives
Input data
Status word
Frequency actual value
Actual value 2 (Not used)
1)
Power
1)
DC bus voltage
Description
Enables communication between the
drive and the fieldbus adapter module.
Enables fieldbus A communication fault
monitoring.
Modbus
register
(4)00051
(4)00052
(4)00053
(4)00054
(4)00055
(4)00056
(4)00057