Copyright © 2018, Juniper Networks, Inc.
mounting shelves until the center-mounting brackets or front-mounting flanges
contact the rack rails or spacer bars (depending on your type of installation). The
shelves ensure that the holes in the mounting brackets and the front-mounting flanges
of the chassis align with the holes in the rack rails.
Install the mounting screws:
6.
Four-post rack or cabinet—Install a mounting screw through each of the holes in
the spacer bars.
Open-frame rack—Install a mounting screw into each of the open mounting holes
aligned with the rack, starting from the bottom.
Loosen the captive screws on the installation handle completely, and remove the
7.
handle from the chassis.
Visually inspect the alignment of the router. If the router is installed properly in the
8.
rack, all the mounting screws on one side of the rack should be aligned with the
mounting screws on the opposite side and the router should be level.
Figure 51: Installing the T320 Router in the Rack
Chapter 18: Installing the T320 Without a Mechanical Lift
141