T320 Environmental Specifications
Related
Documentation
T320 Chassis Grounding Cable and Lug Specifications
Copyright © 2018, Juniper Networks, Inc.
T320 Router Description on page 3
T320 Chassis Description on page 13
T320 Environmental Specifications on page 93
Table 50 on page 93
specifies the environmental specifications required for normal router
operation. In addition, the site should be as dust-free as possible.
Table 50: Router Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the router only in restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
T320 Router Description on page 3
T320 Chassis Description on page 13
T320 Physical Specifications on page 92
WARNING:
Power plant ground and chassis ground must be connected to
the same building ground.
You must provide grounding cables that meets these requirements:
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping crate: –40°F (–40°C)
to 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
DC power: 28,498 BTU/hour (8350 W)
Chapter 9: Preparation Overview
93