MOTOR
FLA
VOLTAGE
RATIO
65-111
200:1
A
112-224
350:1
A
208-600
225-829
A
700:1
830-1790
A
1400:1
11-18
200:1
C
19-37
B
200:1
2300-4160
38-123
200:1
A
124-264
350:1
A
265-518
700:1
A
FIG. 38 – CM-2 CURRENT MODULE – INTERFACE, CURRENT TRANSFORMERS & VARIABLE RESISTORS
YORK INTERNATIONAL
CT
RES
D
(OHMS)
R = 1.282 (CT RATIO)
FLA
R = 0.247 (CT RATIO)
FLA
R = 0.370 (CT RATIO)
FLA
R = 0.740 (CT RATIO)
FLA
NOTES:
A. Requires passing motor lead through current transformer (CT)
once before connecting to power supply.
B. Requires passing motor lead through CT twice before con nect ing
to power supply.
C. Requires passing motor lead through CT three times before con-
necting to power supply.
D. Calculates resistance of "RES" to achieve 1.0VDC at FLA.
FORM 160.54-M1(503)