SI0058 - SOFTWARE ENHANCEMENTS EFFECTIVE FEBRUARY 2003 (CONT'D)
In addition to standard VSD Cycling messages, the following Cycling shutdown messages apply to this VSD:
"VSD – Low Phase A Inverter Baseplate Temperature"
The chiller has shutdown because the Baseplate temperature has decreased to <37 ºF.
"VSD – Low Phase B Inverter Baseplate Temperature"
Same as phase A above.
"VSD – Low Phase C Inverter Baseplate Temperature"
Same as phase A above.
In addition to standard VSD Safety shutdown messages, the following Safety shutdown messages apply to this
VSD:
"VSD – High Phase A Inverter Baseplate Temperature"
The chiller has shutdown because the Baseplate temperature has increased to >158 ºF.
"VSD – High Phase B Inverter Baseplate Temperature"
Same as phase A above.
"VSD – High Phase C Inverter Baseplate Temperature"
Same as phase A above.
"Harmonic Filter – High Baseplate Temperature"
The chiller has shutdown because the Baseplate temperature has increased to >194 ºF.
Microgateway
In previous Flash Card versions, "Start Inhibit" and "Modifi ed Run" codes were transmitted into "Cycling" and
"Safety" shutdown slots in the Microgateway. This alarmed external devices that a Cycling or Safety shutdown
has occurred, when in reality, a Start Inhibit such as Anti-recycle or a Modifi ed Run event such as Current Limit is
in effect. This was incorrect operation. In this version, the codes are transmitted into the proper slots in the Micro-
gateway.
Security Log Screen
In previous Flash Card versions, some setpoint changes were not logged in metric mode. All setpoint changes are
now logged.