Ohm resistor that is soldered to board. It is not
a shunt jump er.
IN: 256K
OUT: 64K or 128K. Should be OUT for YK
chiller applications.
JP39 - Solid State Starter style.
Note: On Variable speed Drive ap pli ca tions,
this jumper must be IN.
IN: Mod "A" - Old style with Logic Board
mount ed in OptiView Con trol Center.
OUT: Mod "B" - New style with integrated
Log ic/Trig ger Board mounted Starter cabinet.
JP40 - Not Used
JP43, JP44 – Display Controller (U29) type (rev "E" and
later boards only). Must be positioned ac cord ing to
the Display Con trol ler type in stalled on Microboard.
Confi gured at the time the board is man u fac tured and
should not require fi eld con fi g u ra tion.
TABLE 2 - MICROBOARD PROGRAM SWITCHES
SW1
1 -
Not Used
2 -
Oil Pump style - Confi gures Program op er a tion
for either Variable Speed Drive oil pump or fi xed
speed oil pump. Chillers equipped with the vari-
able speed oil pump have a program controlled
oil heater and a different complement of so le noid
valves than chillers equipped with a fi xed speed
oil pump.
ON: (Style D/E/F) Variable Speed Oil Pump
- Con fi g ures the Program to operate the Oil
Pump Vari able Speed Drive, the oil heater and
the fol low ing So le noid Valves: Oil Return and
Liq uid Line (J com pres sors only) connected in
par al lel to TB 1-6 1.
OFF: (Style C) Fixed Speed Oil Pump - Con fi g ures
the Program to operate the fi xed speed Oil Pump
and the fol low ing Solenoid Valves: TB1-34 Liquid
Line, TB1-61 Oil Return and Vent Line con nect ed
in parallel, TB1-62 High Speed Thrust.
3 -
Prerun - Determines the duration of the "Sys tem
Prelube" period.
ON: Extended prerun. "System Prelube" pe ri od
is 180 seconds in duration. Oil Pump runs for
167 seconds.
OFF: Standard prerun. "System Prelube" pe ri od
is 50 seconds in duration. Oil Pump runs for 37
seconds.
YORK INTERNATIONAL
Pins 1-2: Type 65548
Pins 2-3: Type 65550
JP41, JP42 - High Speed Thrust Bearing Proximity
Probe type (Not applicable to "P" compres-
sors and style F and later chillers with "G" and
"H5-8" compressors). Refer to Sec tion 13 to
de ter mine which Probe is present.
IN: Universal +12/24VDC Probe, part number
025-xxxxx-000.
OUT: +24VDC Probe, part number
025-30961-000 or 025-35900-000.
JP43, JP44 - Display Controller (U29) type (rev "E"
and later boards only). Must be positioned ac-
cord ing to the Display Con trol ler type in stalled
on Microboard. Configured at the time the
board is man u fac tured and should not require
fi eld con fi g u ra tion.
Pins 1-2: Type 65548
Pins 2-3: Type 65550
4 -
Diagnostics - Enables or disables software di ag -
nos tics.
ON: Enables software diagnostics. Disables
nor mal chiller operation.
OFF: Disables software diagnostics. Enables
normal chiller operation.
5 -
Auto-restart - Determines the course of action
re quired to restart the chiller, if a power failure
occurs while the chiller is running.
ON: Chiller will automatically restart when
pow er is restored.
OFF: Requires a manual reset after power is
restored. The chiller will not start until the op-
er a tor moves the keypad START-RUN-STOP/
RESET rock er switch to the STOP/RESET
po si tion. If in LO CAL mode, the chiller can
then be re start ed by initiating a local start. If in
RE MOTE mode, the chiller will restart upon
re ceipt of a remote start signal .
6 -
Anti-recycle - Enables or disables the anti-recy-
cle tim er.
The anti-recycle timer must NEVER be
disabled unless it is ab so lute ly nec es -
sary to do so during trou ble shoot ing.
FORM 160.54-M1(503)