Liquid Crystal Display
Installation:
Not available at this time.
LG Semicon LP104V2-W Display (refer to Fig. 29)
Removal:
The Lamp slides into the Display from left to right and
is secured with a screw.
1. Remove Control Power from the OptiView Con trol
Cen ter.
2. Remove protective cover from rear of Display.
3. Disconnect Lamp AC power connector from Back-
light Inverter Board.
FIG. 18 – DISPLAY, MOUNTING
48
4. Using small Phillips screwdriver, remove lamp
re tain ing screw.
5. Grasp Lamp AC power connector and gently pull
until Lamp housing is completely removed from
the Display.
Installation:
1. Slide new Lamp into Display from left to right until
Lamp housing is fully inserted.
2. Secure Lamp with Lamp retaining screw.
3. Connect Lamp AC power connector to Back light
Inverter Board.
4. Apply AC power to OptiView Control Center.